2006-07-26 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE MAXIMUM PRESSURE OF -57.5 PSF
 LISTED IN THE PRODUCT APPROVAL IS TOO
 LOW FOR ROOF ZONES 2 & 3 (EDGES AND
 PERIMETERS). FBC TABLE 1606.2B SPECIFIES
 AN UPLIFT PRESSURE OF -68.1 PSF FOR
 ZONES 2 & 3 FOR STRUCTURES WITH 4:12
 PITCH UP TO 30 MEAN ROOF HEIGHT IN
 EXPOSURE B AND 140 MPH WIND SPEED.
  
 3) LIMITATION NUMBER 1 ON PAGE 5 ALLOWS
 INCREASED DESIGN PRESSURE THROUGH
 RATIONAL ANALYSIS PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED ENGINEER,
 ARCHITECT OR ROOF CONSULTANT. SUBMIT
 SIGNED AND SEALED CALCULATIONS.
  