2006-07-24 00:00:00 | ******DENIED****** |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR PLUMBING PLAN REVIEW: |
| |
| 1. PER FBC-2004, CHAPTER 1, SECTION |
| 106.1.3, QUALITY OF BUILDING PLANS: THE |
| BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| DEPARTMENTAL POLICY, STANDARDS FOR PLANS |
| AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| CONFORMITY TO ITS RECORD RETENTION |
| PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, |
| CLARITY, OR OTHER ITEMS RELATED TO |
| RECORDS MANAGEMENT.(NOTE: DRAWINGS |
| SUBMITTED IN PENCIL ARE UNACCEPTABLE) |
| 2. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| 3. PER FBC-2004, PLUMBING, SECTION 708 |
| CLEANOUTS SHALL BE LOCATED AS FOLLOWS: |
| (A) 708.3.4 BASE OF STACK. A CLEANOUT |
| SHALL BE PROVIDED AT THE BASE OF EACH |
| WASTE OR SOIL STACK |
| (B) 708.3.5 BUILDING DRAIN AND BUILDING |
| SEWER JUNCTION. THERE SHALL BE A |
| CLEANOUT NEAR THE JUNCTION OF THE |
| BUILDING DRAIN AND THE BUILDING SEWER. |
| 4. PER FBC-2004, PLUMBING, SECTION 909.1 |
| WET VENT PERMITTED: ONLY THE FIXTURES |
| WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| TO THE WET-VENTED HORIZONTAL BRANCH |
| DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| DISCHARGE DOWNSTREAM OF THE WET VENT. |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. PLEASE SEE ATTACHED ISOMETRIC |
| PLUMBING RISER DIAGRAM IN RED INK FOR |
| REFERENCE FOR RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |