Date |
Text |
2006-07-24 00:00:00 | ******DENIED****** |
| REFERENCE: FBC-2004 FUEL GAS |
| FBC-2994 CHAPTER 1 |
| |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR GAS PLAN REVIEW: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. (PLEASE REFERENCE THE |
| ATTACHED SAMPLE ISOMETRIC GAS RISER |
| DIAGRAM AND INDICATE THE LENGTHS OF THE |
| ABOVE GROUND PIPE ON THE ISOMETRIC FOR |
| RESUBMITTAL.) |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, AND ALL PIPE SIZES. (PLEASE |
| INDICATE THIS ON THE ISOMETRIC.) |
| 3. TYPE OF GAS, (LP OR NATURAL) (PLEASE |
| INDICATE GAS TYPE ON ISOMETRIC.) |
| 4. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). (NOTE: ADDRESS INDICATES |
| EXISTING GAS, PLEASE SEE ATTACHED PERMIT |
| INFORMATION FOR REFERENCE, THE BTU LOAD |
| OF THE EXISTING SYSTEM PLUS THE BTU LOAD |
| OF THE GENERATOR NEED TO BE INDICATED ON |
| THE ISOMETRIC OR INDICATE METER FOR |
| GENERATOR ONLY ON ISOMETRIC.) |
| 5. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4).(PLEASE |
| INDICATE THIS ON THE ISOMETRIC) |
| 6. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| (PLEASE INDICATE THIS ON THE ISOMETRIC.) |
| 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2 (NOTE: |
| NEED MANUFACTURE SHEETS OF THE 2LB TO |
| 11" WC MP REGULATOR) |
| 8. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. PLEASE SEE ATTACHED ISOMETRIC GAS |
| RISER DIAGRAM FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |
| |
| |
| |
| |
| |
| |
| |