Plan Review Notes For Permit 06070993 |
Permit Number |
06070993 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-08-12 15:38:00 | ** DENIED ** | | | | 1) NOTE: PLEASE SEE THE KITCHEN LTS, BATH LTS/GFI WHICH | | SUPPOSE TO BE EXISTING ARE SHOWN ON WITH THE KITCHEN | | RECEPTACLE WITH A LOAD OF 1500VA AS A SMALL APPLIANCE | | CIRCUIT. | | 210.52B1, DOES NOTE PERMIT THIS. | | | | PLEASE CALL IF THERE ARE ANY QUESITONS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | | 561-805-6717 |
|