Plan Review Notes
Plan Review Notes For Permit 06070993
Permit Number 06070993
Review Stop E
Sequence Number 3
Notes
Date Text
2007-08-12 15:38:00** DENIED **
  
 1) NOTE: PLEASE SEE THE KITCHEN LTS, BATH LTS/GFI WHICH
 SUPPOSE TO BE EXISTING ARE SHOWN ON WITH THE KITCHEN
 RECEPTACLE WITH A LOAD OF 1500VA AS A SMALL APPLIANCE
 CIRCUIT.
 210.52B1, DOES NOTE PERMIT THIS.
  
 PLEASE CALL IF THERE ARE ANY QUESITONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 561-805-6717