Plan Review Notes For Permit 06070978 |
Permit Number |
06070978 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-08-09 00:00:00 | | | | | ******PROVISO****** | | FBC-2004 SEC. 424.2.9, OR FBCR-2004 | | SEC. R4101.9 WATER SUPPLY, LOCAL ORD. | | #2853-95, BACKFLOW REQUIRED ON WATER | | SERVICE.(ADD TO NOTES) | | | | FBC-2004 SEC. 424.2.12.1, OR FBCR-2004 | | SEC. R4101.12.1 PRESSURE TESTS. PER | | MANUFACTURE RECOMMENDATIONS, NO AIR TEST | | SHALL BE APPROVED FOR PVC PIPE AND | | FITTINGS. (ADD TO NOTES) | | | | FBC-2004 SEC. 424.2.14.4, OR FBCR-2004 | | SEC. R4101.14.4 CONNECTIONS, ALL WATER | | HEATING EQUIPMENT SHALL BE INSTALLED | | WITH FLANGES OR UNION CONNECTIONS | | ADJACENT TO THE HEATER. | | (ADD TO NOTES) | | | | FBC-2004 SEC. 424.2.14, OR FBCR-2004 | | SEC. R4101.15 GAS PIPING SHALL COMPLY | | WITH FBC FUEL GAS.SEPARATE PLANS AND | | PERMIT REQUIRED. | | | | | | | | |
|