Plan Review Notes
Plan Review Notes For Permit 06070947
Permit Number 06070947
Review Stop P
Sequence Number 2
Notes
Date Text
2006-10-30 10:07:56PASSED/PROVISO
  
 THE SINK IN ROOM 106 SHALL BE ACCESSIBLE AND SHAL
 COMPLY WITH SECTION 11-4.24 & ALL SUBSECTIONS. FORWARD
 APPROACH CLEAR FLOOR SPACE IS REQUIRED AND THE CABINET
 DOORS ARE NOT APPROVED.
 THE DRINKING FOUNTAIN SHALL BE ACCESSIBLE AND SHALL
 COMPLY WITH SECTION 11-4.15 & ALL SUBSECTIONS.
 IN THE REMOVAL OF ANY PART OF THE SANT. SYSTEM, DEAD
 ENDS ARE PROHIBITED. 704.5
 WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURES, NOT IS THE CEILING. PDI-WH 201 (NEW FIXTURES)