Plan Review Notes
Plan Review Notes For Permit 06070947
Permit Number 06070947
Review Stop P
Sequence Number 1
Notes
Date Text
2006-08-19 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
 1. SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES PER TABLES 1004.1.2 AND
 403.1. SHOW THE LOCATION OF ALL
 FIXTURES, INCLUDING WATER CLOSETS, LAVS,
 DRINKING FOUNTAINS.
  
 2. SUBMIT SANT. AND WATER RISER DIAGRAMS
 SHOWING THE DEMO'ED CAPPED, PIPING. SEE
 GENERAL DEMOLITION NOTES NUMBER 21.
 PLEASE INDICATE HOW MANY FLOORS ARE IN
 THIS BUILDING. SECTIONS 106.1.1 AND
 106.3.5.1.3.
  
 3. SHT P0.1 SIGNATURE REQUIRED ON THE
 DATED SEAL PER FAC 61G15.002(2).
 INITIALS ARE NOT ACCEPTABLE. SIGNATURE
 SHALL REFLECT THE SIGNATURE ON FILE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]