Plan Review Notes For Permit 06070947 |
Permit Number |
06070947 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-08-19 00:00:00 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | | | 1. SUBMIT CALCULATIONS FOR MINIMUM | | FACILITIES PER TABLES 1004.1.2 AND | | 403.1. SHOW THE LOCATION OF ALL | | FIXTURES, INCLUDING WATER CLOSETS, LAVS, | | DRINKING FOUNTAINS. | | | | 2. SUBMIT SANT. AND WATER RISER DIAGRAMS | | SHOWING THE DEMO'ED CAPPED, PIPING. SEE | | GENERAL DEMOLITION NOTES NUMBER 21. | | PLEASE INDICATE HOW MANY FLOORS ARE IN | | THIS BUILDING. SECTIONS 106.1.1 AND | | 106.3.5.1.3. | | | | 3. SHT P0.1 SIGNATURE REQUIRED ON THE | | DATED SEAL PER FAC 61G15.002(2). | | INITIALS ARE NOT ACCEPTABLE. SIGNATURE | | SHALL REFLECT THE SIGNATURE ON FILE. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|