Date |
Text |
2007-03-07 18:08:29 | DENIED |
| REFERNCE: FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| |
| FROM PREVIOUS REVIEWS |
| |
| A. OK |
| B. OK |
| |
| C.THE FOLLOWING INFORMATION IS |
| REQUIRED FOR REVIEW FOR GAS PERMIT: |
| |
| 1. OK |
| 2. OK |
| 3. OK |
| 4. OK |
| 5. OK |
| 6. N/A |
| 7. OK |
| 8.N/A |
| 9. OK |
| |
| ************NEW COMMENTS************* |
| |
| A. NEW PLANS WITH NEW INFORMATION REQUIRE NEW COMMENTS. |
| NOW LP-GAS ALSO INDICATED ON PLANS. |
| |
| 1B. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. - THE LENGTHS OF PIPE SHOWN ON THE |
| ISOMETRIC DO NOT REFLECT THE LENGTHS OF PIPE AS SCALED |
| ON THE 1/8" SCALE FLOOR PLAN.SCALE INDICATES THE |
| TOTAL DEVELOPED LENGTH ON THE NATURAL GAS SYSTEM TO BE |
| APPROX. 131'. PLEASE CLARIFY. SECTION 106.1.1.-- SHOW |
| THE SHUT OFF VALVE UPSTREAM OF THE REGULATORS. SECTION |
| 409.4. A DRIP/SEDIMENT TRAP IS REQUIRED DOWNSTREAM OF |
| THE EQUIPMENT SHUT OFF VALVE. SECTIONS 408.2 & 408.4. |
| |
| 2B. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). - AS INDICATED IN COMMENT |
| 1B. THE TOTAL DEVELOPED LENGTH APPEARS TO BE ABOUT |
| 131'. PLEASE VERIFY. SECTION 106.1.1. |
| |
| 3B. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE |
| SECOND STAGE REGULATORS FOR THE NATURAL GAS AND LP GAS |
| SYSTEMS. THE REGULATORS SHALL BE LISTED AND INDICATE |
| THE MODEL NUMBER FOR EACH REGULATOR ON MANUF. |
| SPECIFICATION SHEETS. SECTION 410.2((2)(3). |
| |
| 4B. SUBMIT THE MANUF. SPECIFICATIONS FOR THE "AUTOMATIC |
| TRANSFER SOLENOID SWITCH" INDICATED ON THE STANDBY |
| GENERATOR MECHANICAL PLAN. THIS SOLENOID TRANSFER |
| SWITCH SHALL BE LISTED FOR BOTH NATURAL GAS AND LP GAS |
| AND SHALL INDICATE INSTALLATION INSTRUCTIONS. SECTION |
| 106.1.2. |
| |
| 5B. SHOW THE PIPE SIZE OF THE EXISTING NATURAL GAS LINE |
| FROM THE NATURAL GAS METER TO THE POINT OF CONNECTION |
| OF THE NEW PE PIPE. ALSO INDICATE THE MATERIAL OF THAT |
| EXISTING PIPE. SECTION 106.1.2 AND TABLES 402.4. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |