Plan Review Notes
Plan Review Notes For Permit 06070850
Permit Number 06070850
Review Stop G
Sequence Number 3
Notes
Date Text
2007-03-07 18:08:29DENIED
 REFERNCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 FROM PREVIOUS REVIEWS
  
 A. OK
 B. OK
  
 C.THE FOLLOWING INFORMATION IS
 REQUIRED FOR REVIEW FOR GAS PERMIT:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. N/A
 7. OK
 8.N/A
 9. OK
  
 ************NEW COMMENTS*************
  
 A. NEW PLANS WITH NEW INFORMATION REQUIRE NEW COMMENTS.
 NOW LP-GAS ALSO INDICATED ON PLANS.
  
 1B. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - THE LENGTHS OF PIPE SHOWN ON THE
 ISOMETRIC DO NOT REFLECT THE LENGTHS OF PIPE AS SCALED
 ON THE 1/8" SCALE FLOOR PLAN.SCALE INDICATES THE
 TOTAL DEVELOPED LENGTH ON THE NATURAL GAS SYSTEM TO BE
 APPROX. 131'. PLEASE CLARIFY. SECTION 106.1.1.-- SHOW
 THE SHUT OFF VALVE UPSTREAM OF THE REGULATORS. SECTION
 409.4. A DRIP/SEDIMENT TRAP IS REQUIRED DOWNSTREAM OF
 THE EQUIPMENT SHUT OFF VALVE. SECTIONS 408.2 & 408.4.
  
 2B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - AS INDICATED IN COMMENT
 1B. THE TOTAL DEVELOPED LENGTH APPEARS TO BE ABOUT
 131'. PLEASE VERIFY. SECTION 106.1.1.
  
 3B. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 SECOND STAGE REGULATORS FOR THE NATURAL GAS AND LP GAS
 SYSTEMS. THE REGULATORS SHALL BE LISTED AND INDICATE
 THE MODEL NUMBER FOR EACH REGULATOR ON MANUF.
 SPECIFICATION SHEETS. SECTION 410.2((2)(3).
  
 4B. SUBMIT THE MANUF. SPECIFICATIONS FOR THE "AUTOMATIC
 TRANSFER SOLENOID SWITCH" INDICATED ON THE STANDBY
 GENERATOR MECHANICAL PLAN. THIS SOLENOID TRANSFER
 SWITCH SHALL BE LISTED FOR BOTH NATURAL GAS AND LP GAS
 AND SHALL INDICATE INSTALLATION INSTRUCTIONS. SECTION
 106.1.2.
  
 5B. SHOW THE PIPE SIZE OF THE EXISTING NATURAL GAS LINE
 FROM THE NATURAL GAS METER TO THE POINT OF CONNECTION
 OF THE NEW PE PIPE. ALSO INDICATE THE MATERIAL OF THAT
 EXISTING PIPE. SECTION 106.1.2 AND TABLES 402.4.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]