Plan Review Notes
Plan Review Notes For Permit 06070850
Permit Number 06070850
Review Stop E
Sequence Number 3
Notes
Date Text
2007-02-25 10:20:27*** UNSAT 2NDREVIEW ***
  
  
 ** THE *RESUB* FEE WAS NOT PAID WHEN PLANS WERE
 RESUBMITTED WHICH IS REQUIRED. PLANS WILL NOT BE
 RELEASED UNTIL FEE IS PAID.
  
 ** ONE COPY OF PLANS AND COPY OF PERMIT APPLICATION
 WILL BE RETAINED BY THIS OFFICE.
  
  
 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST
 ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 PERMIT WAS APPLIED FOR BEFORE THE CODES CHNAGES OF
 DECEMBER 8TH, 2006.
 2004 FBC.
 2002 NFPA-70 (NEC).
 2002 NFPA-72
 2003 NFPA-101
 2002 NFPA-110
 ** THESE CODES ARE REQUIRED AT A MINIMUM FOR THIS TRADE
 REVIEWER; OTHERS MAY BE REQUIRED PER OTHER TRADES OR
 REVIEWER(S).
 PLEASE SEE THERE ARE MANY AREAS ON THE PLANS WHICH
 REFERENCE OLDER CODES FROM PREVIOUS CODES, THESE SHOULD
 BE REVISED ACCORDINGLY.
  
 2) NOTE: PLEASE SEE GAS REVIEW NOTES, AS NO
 MANUFACTURES/SPECS CUTS SHEETS WERE SUBMITTED FOR TANK
 AS PROPOSED.
 GAS PERMIT IS APPLIED FOR AT THIS TIME AND PLANS
 INDICATE UNDER SEPARATE PERMIT?
 PLEASE SEE GAS REVIEW NOTES.
  
 3) NOTE: PLEASE SEE MANUFACTURES SPECS/CUT SHEETS WHICH
 REFLECT A 700AMP BREAKER FEEDING A 600A PANEL WHERE
 PLANS CALL FOR A 600AMP BREAKER AT THIS SAME LOCATION
 FOR THE GENERATOR? PLEASE CORRELATE AND ADJUST AS
 NEEDED.
  
 4) NOTE: PLEASE SEE NOTE #3 ABOVE WITH RESPECT TO
 CONDUCTOR SIZES IF INDEED THE BREAKER IS 700AMPS?
 310.16, 240.4
  
 5) NOTE: PLEASE SEE NOTES ON PLANS MENTIONS TO PLACE
 NEW CIRCUITS INTO PANEL *EM* WHICH ARE NOT LEGALLY
 REQUIRED OR EMERGENCY SYSTEMS REQUIRED CIRCUITS. PLEASE
 SEE THE NEC 700 AND 701 AS 702 TYPE CIRCUITS MAY NOT BE
 IN SAME EQUIPMENT.
 PLEASE DO NOT INDICATE SYSTEMS OTHER THAN MENTIONED
 ABOVE UNLESS INSTALLING ANOTHER 702 SYSTEM WHICH WILL
 REQUIRE A SEPARATE ATS AND LOAD SHEDDING, PANEL
 SCHEDULE, LOADS ETC.
 PLEASE SEE THE LOAD SUMMARY ON PLANS DOES NOT INCLUDE
 ANY OF THESE LOADS MENTIONED IN NOTES.
 PLEASE SUBMIT A COMPLETE PANEL SCHEDULE FOR THE
 EXISTING EM PANEL.
 310.16, 240.4, 215.5, 701.6, 700.6, 702.6, 408.4, ETC
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION.
 PLEASE ALSO SEE CHAPTER 6 OF NFPA-110 2002.
  
 6) NOTE: PLEASE SEE AS STATED IN PREVIOUS REVIEW;
 PLEASE SUBMIT ALL PLANS INTO COMPLETE SETS FOR REVIEW
 AND STAMPING. PLEASE DO NOT SUBMIT LOOSE SHEETS. PLEASE
 BE SURE TO REMOVE ANY OLD/VOIDED SHEETS FROM SHEETS.
  
 7) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE FLOOD
 ELEVATION AS REQUIRED PER CHAPTER 7 OF NFPA-110. PLEASE
 STATE IF THIS ELEVATION IS THAT FROM TEH SLOSH CHARTS
 BASED ON A CAT 4 HURRICANE OR THAT OF THE LEVELS BASED
 ON THE " 100 YR STORM LEVEL".
 7.2.3*
  
 8) NOTE: PLEASE SEE FBC 108.3 AS THE VALUE FOR COMPLETE
 SCOPE OF WORK ON PLANS SHALL INLCUDE ALL LABOUR AND
 MATERIALS FOR ALL SUBS AND EQUIPMENT, EVEN IF EQUIPMENT
 IS OWNER SUPPLIED. PLEASE KNOW A VALUE MAY BE ASSED
 BASED ON FAIR MARKET VALUE BASED ON MARSHALL'S & SWIFT
 GUIDE AS ADOPTED BY THE FBC ADMINSTRATIVE SECTION AS
 NOTED ABOVE.
 AS THE SCOPE OF WORK HAS ONCE AGAIN INCREASED THE VALUE
 HAS NOT BEEN ADJUSTED, PLEASE DO SO OR A VALUE WILL BE
 ASSESSED USING THE FBC AND MARSHALL'S & SWIFT GUIDES.
  
 9) NOTE: THE TIME FOR FUEL CONSUMPTION SHALL BE PLACED
 ON PLANS BASED ON THE "ON-SITE" FUEL.
 THIS WAS NOTED ON PREVIOUS REVIEW.
  
 ** PLEASE KNOW BASED ON THE ELECTRICAL RISER SUBMITTED
 OF THE EXISTING ELECTRICAL SERVICE, THERE ARE SEVERAL
 ITEMS WHICH ARE NOT COMPLIANT FOR THE CURRENT CODES AND
 CODES FOR AT LEAST THE LAST 20 YEARS, THIS REVIEWER IS
 NOT RESPONSIBLE FOR THE EXISTING ELECTRICAL SERVICE AND
 HOW EQUIPMENT IS FED. NO SCOPE OF WORK IS BEING APPLIED
 FOR TO UPDATE OR DO WORK WITH THE EXISTING SERVICE AS
 SHOWN.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  