Plan Review Notes For Permit 06070850 |
Permit Number |
06070850 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-02-26 07:41:56 | | | | | BUILDING PLAN REVIEW | | PERMIT:06070850 | | ADD:5200 N. FLAGLER DR. | | CONT: PALM BEACH AIR INC. | | TEL: (561)833-3030 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 1ST | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2)FBC. 106.1 SUBMIT TWO COMPLETE SETS OF DRAWINGS. | | | | 3) 2004 FL. BLD CODE 1603.1.4 THE | | FOLLOWING INFORMATION RELATED TO WIND | | SHALL BE SHOWN ON THE CONSTRUCTION | | DRAWINGS, | | 1)- BASIC WIND SPEED, MPH | | 2)- WIND IMPORTANCE FACTOR, & BUILDING | | CATEGORY | | 3)- WIND EXPOSURE | | 4)- INTERNAL PRESSURE COEFFICIENT, | | 5)- COMPONENTS & CLADDING, THE DESIGN | | WIND PRESSURES IN TERMS OF PSF. | | | | 4)THIS IS A FLOOD ZONE AREA (A-5), THE SLAB SHALL BE | | AT LEAST SIX INCHES ABOVE THE BASE FLOOD ELEVATION(7 | | FT.) | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 |
|