Plan Review Notes
Plan Review Notes For Permit 06070850
Permit Number 06070850
Review Stop G
Sequence Number 2
Notes
Date Text
2006-10-30 08:42:45DENIED
 REFERNCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 A. OK
 B. OK
  
 C. SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR
 REVIEW FOR GAS PERMIT:
  
 1. OK
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE
 NOTED, BUT GALVANIZED PIPE IS NOT APPROVED FOR
 UNDERGROUND PER SECTION 404.8.
  
 3. OK
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 ****RESPONSE NOTED, BUT THE MAXIMUM LOAD ON THE 2" PIPE
 PER TABLE IS 1,300,000 BTU'S.1,717,000 BTU'S SHOWN.
 MINIMUM 2-1/2" PIPE REQUIRED.
  
 5. OK
 6. N/A
 7. OK
 8.N/A
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 INSTALLATION INSTRUCTIONS SHALL BE
 SUBMITTED TO DETERMING THE DISTANCE FROM
 STRUCTURES/WALLS REQUIRED.
 ****NO RESPONSE NOTED, NOT ADDRESSED
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]