Plan Review Notes For Permit 06070850 |
Permit Number |
06070850 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-10-30 08:42:45 | DENIED | | REFERNCE: FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | | | A. OK | | B. OK | | | | C. SEPARATE GAS PERMIT REQUIRED. THE | | FOLLOWING INFORMATION IS REQUIRED FOR | | REVIEW FOR GAS PERMIT: | | | | 1. OK | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE | | NOTED, BUT GALVANIZED PIPE IS NOT APPROVED FOR | | UNDERGROUND PER SECTION 404.8. | | | | 3. OK | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | ****RESPONSE NOTED, BUT THE MAXIMUM LOAD ON THE 2" PIPE | | PER TABLE IS 1,300,000 BTU'S.1,717,000 BTU'S SHOWN. | | MINIMUM 2-1/2" PIPE REQUIRED. | | | | 5. OK | | 6. N/A | | 7. OK | | 8.N/A | | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | INSTALLATION INSTRUCTIONS SHALL BE | | SUBMITTED TO DETERMING THE DISTANCE FROM | | STRUCTURES/WALLS REQUIRED. | | ****NO RESPONSE NOTED, NOT ADDRESSED | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|