Plan Review Notes For Permit 06070850
Permit Number 06070850
Review Stop E
Sequence Number 2
Notes
Date Text
2006-10-14 19:38:24*** UNSAT2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME
 NEW NOTES FOR PLANS SUBMITTED WHICH NOW INDICATE ITEMS
 NEEDED ON PREVIOUS REVIEW.
  
 1) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT
 SHEETS FOR ALL NEW EQUIPMENT WHICH WILL BE INSTALLED.
 PLEASE ALSO KNOW SOME COMMENTS BELOW WILL REQUIRE OTHER
 SPECS (TANK).
  
 2) NOTE: PLEASE SEE 700.12B3 AND 701.11B3 AS ON SITE
 FUEL IS REQUIRED FOR THE MINIMUM AMOUNT OF TIME
 REQUIRED FOR BOTH EM AND LEGALLY REQUIRED."PRIME MOVERS
 SHALL NOT BE SOLELY DEPENDENT ON A PUBLIC UTILITY GAS
 SYSTEM FOR THEIR FUEL SUPPLY OR MUNICIPAL WATER SUPPLY
 FOR THEIR COOLING SYSTEMS. MEANS SHALL BE PROVIDED FOR
 AUTOMATICALLY TRANSFERRING FROM ONE FUEL SUPPLY TO
 ANOTHER WHERE DUAL FUEL SUPPLIES ARE USED."
  
 3) NOTE: PLEASE SEE NFPA-20 2003 9.6.2.2 THE FUEL
 SUPPLY CAPACITY SHALL BE SUFFICIENT TO PROVIDE 8 HOURS
 OF FIRE PUMP OPERATION AT 100 PERCENT OF THE RATED PUMP
 CAPACITY IN ADDITION TO THE SUPPLY REQUIRED FOR OTHER
 DEMANDS.
 THIS IS REQUIRED FOR "ONSITE" FUEL.
  
 4) NOTE: PLEASE SEEE NFPA-110 7.2.3*, THIS UNIT IS
 LOCATED IN A "FLOOD ZONE A, (SEE BLDG REVIEW ALSO).
 PLEASE PROVIDE COMPLETE ELEVATION FOR THIS TO MEET THE
 MIN LEVELS FOR EITHER ONE OF THE FOLLOWING. 100YR STORM
 ELEVATION OR BASED ON A CAT 4 STORM FROM THE "SLOSH"
 PREDICTION CHARTS.
  
 5) NOTE: PLEASE SEE PLUMB REVIEW COMMENTS FOR TYPE OF
 MATERIALS REQUIRED FOR GAS LINE PER 7.9.3.1GALVANIZED
 FUEL LINES SHALL NOT BE USED.
  
 6) NOTE: PLEASE SEE WE ARE UNABLE TO VERIFY THE AIC
 RATING FOR EQUIPMENT AT THIS TIME DUE TO GEN SPEC NOT
 SUBMITTED.
 PLEASE SEE 110.9, 240.12 FOR DETAIL ON SELECTIVE
 COORDINATION. PLEASE ALSO INDICATE LET THROUGH AND THE
 EXSITING RATING FOR THE EM PANEL MAIN.
  
 7) NOTE: PLEASE SEE FBC 108.3 AS THE VALUE FOR COMPLETE
 SCOPE OF WORK ON PLANS SHALL INLCUDE ALL LABOUR AND
 MATERIALS FOR ALL SUBS AND EQUIPMENT, EVEN IF EQUIPMENT
 IS OWNER SUPPLIED. PLEASE KNOW A VALUE MAY BE ASSED
 BASED ON FAIR MARKET VALUE BASED ON MARSHALL'S & SWIFT
 GUIDE AS ADOPTED BY THE FBC ADMINSTRATIVE SECTION AS
 NOTED ABOVE.
  
  
 *** PLEASE KNOW AS SOME INFORMATION IS NOT YET
 SUBMITTED, THERE MAY BE FUTURE COMMENTS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  