2006-10-14 19:38:24 | *** UNSAT2ND REVIEW *** |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME |
| NEW NOTES FOR PLANS SUBMITTED WHICH NOW INDICATE ITEMS |
| NEEDED ON PREVIOUS REVIEW. |
| |
| 1) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT |
| SHEETS FOR ALL NEW EQUIPMENT WHICH WILL BE INSTALLED. |
| PLEASE ALSO KNOW SOME COMMENTS BELOW WILL REQUIRE OTHER |
| SPECS (TANK). |
| |
| 2) NOTE: PLEASE SEE 700.12B3 AND 701.11B3 AS ON SITE |
| FUEL IS REQUIRED FOR THE MINIMUM AMOUNT OF TIME |
| REQUIRED FOR BOTH EM AND LEGALLY REQUIRED."PRIME MOVERS |
| SHALL NOT BE SOLELY DEPENDENT ON A PUBLIC UTILITY GAS |
| SYSTEM FOR THEIR FUEL SUPPLY OR MUNICIPAL WATER SUPPLY |
| FOR THEIR COOLING SYSTEMS. MEANS SHALL BE PROVIDED FOR |
| AUTOMATICALLY TRANSFERRING FROM ONE FUEL SUPPLY TO |
| ANOTHER WHERE DUAL FUEL SUPPLIES ARE USED." |
| |
| 3) NOTE: PLEASE SEE NFPA-20 2003 9.6.2.2 THE FUEL |
| SUPPLY CAPACITY SHALL BE SUFFICIENT TO PROVIDE 8 HOURS |
| OF FIRE PUMP OPERATION AT 100 PERCENT OF THE RATED PUMP |
| CAPACITY IN ADDITION TO THE SUPPLY REQUIRED FOR OTHER |
| DEMANDS. |
| THIS IS REQUIRED FOR "ONSITE" FUEL. |
| |
| 4) NOTE: PLEASE SEEE NFPA-110 7.2.3*, THIS UNIT IS |
| LOCATED IN A "FLOOD ZONE A, (SEE BLDG REVIEW ALSO). |
| PLEASE PROVIDE COMPLETE ELEVATION FOR THIS TO MEET THE |
| MIN LEVELS FOR EITHER ONE OF THE FOLLOWING. 100YR STORM |
| ELEVATION OR BASED ON A CAT 4 STORM FROM THE "SLOSH" |
| PREDICTION CHARTS. |
| |
| 5) NOTE: PLEASE SEE PLUMB REVIEW COMMENTS FOR TYPE OF |
| MATERIALS REQUIRED FOR GAS LINE PER 7.9.3.1GALVANIZED |
| FUEL LINES SHALL NOT BE USED. |
| |
| 6) NOTE: PLEASE SEE WE ARE UNABLE TO VERIFY THE AIC |
| RATING FOR EQUIPMENT AT THIS TIME DUE TO GEN SPEC NOT |
| SUBMITTED. |
| PLEASE SEE 110.9, 240.12 FOR DETAIL ON SELECTIVE |
| COORDINATION. PLEASE ALSO INDICATE LET THROUGH AND THE |
| EXSITING RATING FOR THE EM PANEL MAIN. |
| |
| 7) NOTE: PLEASE SEE FBC 108.3 AS THE VALUE FOR COMPLETE |
| SCOPE OF WORK ON PLANS SHALL INLCUDE ALL LABOUR AND |
| MATERIALS FOR ALL SUBS AND EQUIPMENT, EVEN IF EQUIPMENT |
| IS OWNER SUPPLIED. PLEASE KNOW A VALUE MAY BE ASSED |
| BASED ON FAIR MARKET VALUE BASED ON MARSHALL'S & SWIFT |
| GUIDE AS ADOPTED BY THE FBC ADMINSTRATIVE SECTION AS |
| NOTED ABOVE. |
| |
| |
| *** PLEASE KNOW AS SOME INFORMATION IS NOT YET |
| SUBMITTED, THERE MAY BE FUTURE COMMENTS. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |