Plan Review Notes
Plan Review Notes For Permit 06070850
Permit Number 06070850
Review Stop G
Sequence Number 1
Notes
Date Text
2006-08-10 00:00:00DENIED
 REFERNCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 A. PLANS SHALL BE SEALED PER SECTION
 106.1.
  
 B. SUBMIT A SITE PLAN SHOWING ALL
 STRUCTURES, WALLS ETC. AJOINING THE
 GENERATOR. SECTION 106.1.2.
  
 C. SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR
 REVIEW FOR GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. N/A
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8.N/A
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 INSTALLATION INSTRUCTIONS SHALL BE
 SUBMITTED TO DETERMING THE DISTANCE FROM
 STRUCTURES/WALLS REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]