Plan Review Notes
Plan Review Notes For Permit 06070850
Permit Number 06070850
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-02 00:00:00************ UNSAT ***********
  
 1) NOTE: PLEASE SEE PLANS SUBMITTED AR
 PHOTO-COPIES OF SIGNEDAND SEALED
 PLANS.
 PLEASE SEE FS 471.025, FAC 61G15-23.002
  
 2) NOTE: PLEASE SEE PLANS NOTE THAT THE
 GEN IS NOT REQUIRED FOR LIFE SAFETY:
 PLEASE PROVIDE INFORMATION FOR WHAT IS
 PROVIDING BACK UP FOR EM SYSTEMS.
 CAN NOT VERIFY CODE COMPLIANCE ITEMS AT
 THIS TIME FOR THIS.
 IS THIS BUIDLING A HIGH-RISE?
 PLEASE SEE 700.12B3
 PLEASE SEE 701.11B3
 PLEASE SEE THAT NO PANEL SCHEDULES,
 INTENDED LOADS ETC WERE SUBMITTED OR
 SHOWN FOR THIS NEW GENERATOR.
  
 3) NOTE: PLEASE PROVIDE AN ELECTRICAL
 DIAGRAM TO VERIFY CONDUCTORS, FEEDERS,
 CONDUITS, OCP ETC ETC.
 PLEASE SEE NO INFORMATION OR ELECTRICAL
 PLANS WERE SUBMITTED SHOWING HOW THIS
 UNIT IS BEING WIRED IN WITH THE EXISTING
 SERVICE.
 PLEASE PROVIDE OCP ON GENERATOR ETC.
 PLEASE PROVIDE AIC RATINGS ETC
 PLEASE SEE NEC 2002.
 THERE ARE TOO MANY CODE ARTICLES TO
 REFERENCE TO COMPLETE PLANS.
 FBC 106.1.2
  
 4) NOTE: PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR NEW GEN, WP
 ENCLOUSURE (IF NOT PART OF GEN) ETC.
 106.1.2, NEC 90.8, 110.3 ETC
  
 ** PLEASE KNOW, PLANS AND SUBMITTED
 PACKAGE IS NOT COMPLETE AT THIS TIME AND
 THERE MAY BE FURTHER COMMENTS ONCE PLANS
 ARE COMPLETE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]