2006-07-16 00:00:00 | ******* UNSAT ********* |
| |
| 1) NOTE: PLEASE SEE THAT PLANS/DESIGN |
| ARE NOT REQUIRED TO BE NOTORIZED, |
| HOWEVER IF THEY ARE , PLEASE SURE THEY |
| ARE NOTORIZED AS REQUIRED UNDER FS |
| 117.05 |
| PLEASE KNOW, THEY ARE ONLY REQUIRED TO |
| CONTAIN THE PRINTED NAME AND SIGNATURE |
| OF THE PERSON/QUALIFIER RESPONSIBLE FOR |
| PLANS/DESIGN. |
| |
| 2) NOTE: PLEASE SEE AN "EQUIPMENT |
| GROUNDING CONDUCTOR" IS BEING SHOWN FROM |
| THE METER TO THE FIRST MEANS OF |
| DISCONNECT WHICH IS PARALLELING THE |
| NEUTRAL. PLEASE SEE 250.6,250.24B, AS |
| THE "EQUIPMENT GROUNDS" ARE ONLY |
| INSTALLED AFTER THE FIRST MEANS OF |
| DISCONNECT. |
| |
| 3) NOTE: PLEASE PROVIDE A "SITE LAYOUT" |
| FOR LOCATION OF THE EQUIPMENT AND WHERE |
| IT IS BEING INSTALLED. |
| PLEASE SEE PLANS MENTIONS 525 OKEECHOBEE |
| BLVD, YET APPLICATION IS FOR 1096 |
| FLORIDA AVE. |
| |
| 4) NOTE: PLEASE KNOW, A RECORDED NOTICE |
| OF COMMENCEMENT WILL BE REQUIRED AS |
| PERMIT APPLICATION REFERENCES THE BLDG |
| PERMIT FOR THE OFFICE BLDG WHICH HAS NOT |
| BEEN ISSUED FOR PERMIT, NOR HAS AN NOC |
| BEEN RECEIVED UNDER THE BLDG PERMIT. |
| PLEASE CHECK WITH CONTRACTOR TO SEE F |
| ONE WAS SUBMITTED FOR FOUNDATION PERMIT. |
| PLEASE KNOW, IF THE DATE OF THE |
| RECORDING OF THE NOC IS OVER 90 DAYS |
| THEN THE NOC BECOMES VOIDE OF WORK HAS |
| NOT COMMENCED. |
| FS 713.13(2). |
| |
| 5) NOTE: PLEASE CLARIFY GROUNDING AT |
| TRAILERS? GRNDS RODS? 250.32, 550.16 |
| PLEASE ALSO KNOW, IF THESE CONTRUCTION |
| TRAILERS CONTTAIN BATHRMS,AND ANY ARE |
| FED BY METAL COLD WATER PIPES, THEN THIS |
| ATTACHMENT SHALL BE PART OF THE |
| GROUNDING ELECTRODE SYSTEMS AT TRAILER |
| AND SERVICE. |
| 250.50 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |