Date Text
2006-07-25 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING AND GAS PLAN REVIEW:(NOTE:
 THE MASTER NUMBER REFERENCED ON THE
 PERMIT APPLICATION HAS NO PLUMBING,
 PLEASE REFERENCE ATTACHED PERMIT
 INFORMATION ON THAT MASTER NUMBER
 05020630)
  
 1. SEPERATE PLANS AND PERMIT REQUIRED
 FOR GAS WORK WITH THE FOLLOWING
 INFORMATION.
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 4. TYPE OF GAS, (LP OR NATURAL)
 5. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 6. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 7. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 8. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 9. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 10. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 11. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 12. MORE INFORMATION IS REQUIRED FOR THE
 ICE BOX HOOK-UP INDICATED ON THE PRINTS:
 (A) THE ICE BOX IS INDICATED AS A NEW
 ITEM NOT A REINSTALL PLEASE INDICATE HOW
 ICE BOX IS TO BE DRAINED PER FBC-2004
 PLUMBING, SECTION 802 INDIRECT WASTES.
 (B) PLEASE INDICATE HOW THE ICE BOX IS
 TO BE SUPPLIED WITH WATER AND PROTECTED
 FROM WATER HAMMER PER FBC-2004 PLUMBING,
 SECTION 604.9.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. (NOTE: THE PERMIT APPLICATION
 ADDRESS DOES NOT MATCH THE ADDRESS IN
 COMPUTER WITH THE PROPERTY I-D NUMBER,
 PLEASE SEE ATTACHED PERMIT INFORMATION
 WITH ADDRESS AND PROPERTY I-D NUMBER FOR
 REFERENCE AND PLEASE CORRELATE FOR THE
 RESUBMITTAL)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  
  
  