Date |
Text |
2006-07-25 00:00:00 | ******DENIED****** |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR PLUMBING AND GAS PLAN REVIEW:(NOTE: |
| THE MASTER NUMBER REFERENCED ON THE |
| PERMIT APPLICATION HAS NO PLUMBING, |
| PLEASE REFERENCE ATTACHED PERMIT |
| INFORMATION ON THAT MASTER NUMBER |
| 05020630) |
| |
| 1. SEPERATE PLANS AND PERMIT REQUIRED |
| FOR GAS WORK WITH THE FOLLOWING |
| INFORMATION. |
| 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| 3. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| 4. TYPE OF GAS, (LP OR NATURAL) |
| 5. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| 6. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| 7. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| GAS CODE SECTION 304. |
| 8. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| 9. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2004 FUEL GAS CODE |
| SECS. 502 THRU 505. |
| 10. SUBMIT MANUFACTURE SHEETS FOR ALL |
| GAS EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2 |
| 11. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| 12. MORE INFORMATION IS REQUIRED FOR THE |
| ICE BOX HOOK-UP INDICATED ON THE PRINTS: |
| (A) THE ICE BOX IS INDICATED AS A NEW |
| ITEM NOT A REINSTALL PLEASE INDICATE HOW |
| ICE BOX IS TO BE DRAINED PER FBC-2004 |
| PLUMBING, SECTION 802 INDIRECT WASTES. |
| (B) PLEASE INDICATE HOW THE ICE BOX IS |
| TO BE SUPPLIED WITH WATER AND PROTECTED |
| FROM WATER HAMMER PER FBC-2004 PLUMBING, |
| SECTION 604.9. |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, PLEASE INCLUDE A |
| TRANSMITTAL LETTER INDICATING HOW EACH |
| ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. (NOTE: THE PERMIT APPLICATION |
| ADDRESS DOES NOT MATCH THE ADDRESS IN |
| COMPUTER WITH THE PROPERTY I-D NUMBER, |
| PLEASE SEE ATTACHED PERMIT INFORMATION |
| WITH ADDRESS AND PROPERTY I-D NUMBER FOR |
| REFERENCE AND PLEASE CORRELATE FOR THE |
| RESUBMITTAL) |
| |
| END OF COMMENTS: |
| |