Plan Review Notes
Plan Review Notes For Permit 06070748
Permit Number 06070748
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-27 00:00:00*** UNSAT **
  
 1) NOTE: PLEASE SEE GEN REQUIRES 3 FT
 FROM HOUSE AND REQUIRES A MIN OF 3' FROM
 ADJOING PROPERTY AS THE NEIGHBORING
 PROPERTY OWNER MAY INSTALL A WALL WHICH
 THEN WOULD NOT HAVE THE 3' MIN CLEARENCE
 REQUIRED. PLEASE SEE SIDE WOULD HAVE TO
 BE 8FT OR MORE.
 PLEASE SEE ZONING ONLY PERMITS GEN 4FT
 INTO THE REQUIRED SET BACK AND IF GEN IS
 3FT OFF WALL AND GEN IS 2FT WIDE, THEN
 THE GEN IS TOO FAR INTO THE ZOING SET
 BACK ALLOWED.
 PLEASE SEE IT SEEMSA REVISED LOCATION
 MAY BE NEEDED.
 110.3,90.7
  
 2) NOTE: PLEASE SEE GROUPING OF
 DISCONNECTING MEANS CAN NOT YET BE
 VERIFIED AS THE NEW DISCONNECT BEING
 NOTED IS NOT SHOWN ON PLANS GROUPED.
 PLEASE PROVIDE A LAYOUT OF THE MAIN AND
 THE NEW DISCONNECT. AS SHOWN ON RISER,
 ALL EQUIPMENT IS OUTSIDE, YET THE SPECS
 FOR THE ATSPANEL SUBMITTED IS A NEMA 1
 LOCATION ONLY.
 PLEASE INDICATE THE OCP FROM THE
 EXISTING PANEL TO NEW SUB PANEL AND
 PELASE INDICATE THE SIZE OF THE NEW
 DISCONNECT/CONDUCTORS.
 240.4,310.16,225.39 225.34, 230.72 ETC
  
 3) NOTE: PLEASE BE SURE ALL
 PLANS/DESIGNS SUBMITTED CONTAINS THE
 PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLANS.
 FBC 106.1.2
  
 ** PLEASE SEE SURE TO COPY ALL PLANS AS
 HANDWRITTEN AND WHITE OUT ON PLANS BEING
 SUBMITTED IS NOT PERMITTED.
 106.1.2,106.1.3,106.1
 FBC
  
 ** IMPORTANT**
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  