Notes
Date Text
2006-07-27 00:00:00****** UNSAT ******
  
 1) NOTE: PLEASE SUBMIT INFORMATION ON
 THE MINIMUM CLEARENCES FOR GENERATOR.
 LTRS OBTAINED BY THIS OFFICE FROM
 MANUFACTURE REQUIRES A MIN OF 3' FROM
 ALL SURROUNDING WALLS/HOUSE ETC.
 110..3/90.7
 PLEASE KNOW, DUE TO THE MIN REQUIRED
 CLEARENCE, AND ZOING SETBACK, GENERATOR
 LOCATION MAY BE REVISED.
  
 2) NOTE: PLEASE SEE MISSING DISCONNECT
 REQUIRED FOR FEEDERS FROM GENERATOR AT
 HOUSE. PLEASE SEE 225.31-225.39.
 THE BRKR ON THE GENERATOR IS NOT
 ACCEPTABLE FOR THE MEANS OF DISC.
  
 3) NOTE: PLEASE SEE THAT ALL PLANS ARE
 REQUIRED TO CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 PLANS/DESIGNS.
 FBC 106.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717