Plan Review Notes For Permit 06070748 |
Permit Number |
06070748 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-07-27 00:00:00 | ****** UNSAT ****** | | | | 1) NOTE: PLEASE SUBMIT INFORMATION ON | | THE MINIMUM CLEARENCES FOR GENERATOR. | | LTRS OBTAINED BY THIS OFFICE FROM | | MANUFACTURE REQUIRES A MIN OF 3' FROM | | ALL SURROUNDING WALLS/HOUSE ETC. | | 110..3/90.7 | | PLEASE KNOW, DUE TO THE MIN REQUIRED | | CLEARENCE, AND ZOING SETBACK, GENERATOR | | LOCATION MAY BE REVISED. | | | | 2) NOTE: PLEASE SEE MISSING DISCONNECT | | REQUIRED FOR FEEDERS FROM GENERATOR AT | | HOUSE. PLEASE SEE 225.31-225.39. | | THE BRKR ON THE GENERATOR IS NOT | | ACCEPTABLE FOR THE MEANS OF DISC. | | | | 3) NOTE: PLEASE SEE THAT ALL PLANS ARE | | REQUIRED TO CONTAIN THE PRINTED NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR | | PLANS/DESIGNS. | | FBC 106.1.2 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | |
|