Plan Review Notes For Permit 06070735 |
Permit Number |
06070735 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-07-30 00:00:00 | ******* UNSAT ******* | | | | 1) NOTE: PLEASE INDICATE ALL CIRCUITING | | ON PLANS AND CORRELATE WITH THE | | SUBMITTED PANEL SCHEDULE. | | PLEASE SEE PANE SCHEDULE SHOWS 6 | | CIRCUITS FOR GNE LTS AND RECEPTS | | FBC 106.1.2, | | 408.4,240.4,310.16 | | | | 2) NOTE: PLEASE PROVIDE ALL ROOM AND | | AREA DESIGNATIONS ON PLANS. | | 106.1.2 | | PLEASE BE SURE ROOMS AND AREAS ARE | | IDENTIFIED ON PANEL SCHEDULE. | | 408.4. | | IE: BEDRM LTS, KLIVING RM RECEPTSETC. | | | | 3) NOTE: PLEASE SEE 210.11C1,220.16 A | | THE VA FOR EACH OF THE SMALL APPL | | CIRCUITS SHOULD BE 1500VA. PLEASE SEE 3 | | CIRCUITS ARE SHOWN HOWEVER LOAD IS ONLY | | SHOWN FOR TWO. | | | | 4) NOTE: PLEASE SEE BATH GFI RECEPT IS | | BEING SHOWN ON A 2POLE 40A BREAKER. THIS | | EXCEEDS RATINGS ETC. | | PLEASE ALSO SEE #6 AWG SHOWN. | | 240.4,310.16,210.11C3 | | | | 5) NOTE: PLEASE SEE THAT A DEDICATED | | WINDOW A/C IS LISTED ON PANEL SCHEDULE, | | HOWEVER PLANS DO NOT SHOW THIS. | | 106.1.2 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | |
|