Plan Review Notes
Plan Review Notes For Permit 06070735
Permit Number 06070735
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-30 00:00:00******* UNSAT *******
  
 1) NOTE: PLEASE INDICATE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULE.
 PLEASE SEE PANE SCHEDULE SHOWS 6
 CIRCUITS FOR GNE LTS AND RECEPTS
 FBC 106.1.2,
 408.4,240.4,310.16
  
 2) NOTE: PLEASE PROVIDE ALL ROOM AND
 AREA DESIGNATIONS ON PLANS.
 106.1.2
 PLEASE BE SURE ROOMS AND AREAS ARE
 IDENTIFIED ON PANEL SCHEDULE.
 408.4.
 IE: BEDRM LTS, KLIVING RM RECEPTSETC.
  
 3) NOTE: PLEASE SEE 210.11C1,220.16 A
 THE VA FOR EACH OF THE SMALL APPL
 CIRCUITS SHOULD BE 1500VA. PLEASE SEE 3
 CIRCUITS ARE SHOWN HOWEVER LOAD IS ONLY
 SHOWN FOR TWO.
  
 4) NOTE: PLEASE SEE BATH GFI RECEPT IS
 BEING SHOWN ON A 2POLE 40A BREAKER. THIS
 EXCEEDS RATINGS ETC.
 PLEASE ALSO SEE #6 AWG SHOWN.
 240.4,310.16,210.11C3
  
 5) NOTE: PLEASE SEE THAT A DEDICATED
 WINDOW A/C IS LISTED ON PANEL SCHEDULE,
 HOWEVER PLANS DO NOT SHOW THIS.
 106.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  