Plan Review Notes
Plan Review Notes For Permit 06070733
Permit Number 06070733
Review Stop B
Sequence Number 1
Notes
Date Text
2006-07-17 00:00:00BUILDING REVIEW CHECKLIST:
 1- ENGINEER IS REFERING TO NOA
 02-1023.05. CORRECT NOA THAT WAS
 SUBMITTED TO OBTAIN THE FLORIDA PRODUCT
 APPROVAL IS NOA 02-0212.07. ENGINEER TO
 CORRECT HIS CALCULATIONS AND REFER TO
 THE CORRECT NOA.
  
 2- ENGINEER TO REVIEW NOA 02-0212.07 AND
 PROVIDE THE REQUIRED RAS 117
 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS. THIS SYSTEM
 IS COMPLETELY DIFFERENT THAN ONE FOR
 WHICH CALCULATIONS WERE DONE. SEE PAGE 7
 OF THE NOA.
  
 3- PERMIT APPLICATION SPECIFIES THAT
 ROOF HAS "NO SLOPE PONDING WATER SPEC".
 ROOFS FOR RE-ROOFING PERMITS NEED NOT TO
 HAVE THE REQUIRED SLOPE OF 1/4 PER FOOT
 RULE, BUT ROOF MUST PROVIDEPOSITIVE
 ROOF DRAINAGE. SEE SECTION 1510.1 FBC
 2004.
  
 4- LAST PAGE OF ENGINEER REPORT IS
 LISTING ALL ZONES AS ZONE 1. WHEN DOING
 CALCULATIONS FOR CORRECT NOA (SEE ITEMS
 1 AND 2 ABOVE) MAKE SURE CORRECT ROOF
 ZONES ARE LISTED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712