Plan Review Notes For Permit 06070733 |
Permit Number |
06070733 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-07-17 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1- ENGINEER IS REFERING TO NOA | | 02-1023.05. CORRECT NOA THAT WAS | | SUBMITTED TO OBTAIN THE FLORIDA PRODUCT | | APPROVAL IS NOA 02-0212.07. ENGINEER TO | | CORRECT HIS CALCULATIONS AND REFER TO | | THE CORRECT NOA. | | | | 2- ENGINEER TO REVIEW NOA 02-0212.07 AND | | PROVIDE THE REQUIRED RAS 117 | | CALCULATIONS FOR NAIL ENHANCING AT | | PERIMETER AND CORNER AREAS. THIS SYSTEM | | IS COMPLETELY DIFFERENT THAN ONE FOR | | WHICH CALCULATIONS WERE DONE. SEE PAGE 7 | | OF THE NOA. | | | | 3- PERMIT APPLICATION SPECIFIES THAT | | ROOF HAS "NO SLOPE PONDING WATER SPEC". | | ROOFS FOR RE-ROOFING PERMITS NEED NOT TO | | HAVE THE REQUIRED SLOPE OF 1/4 PER FOOT | | RULE, BUT ROOF MUST PROVIDEPOSITIVE | | ROOF DRAINAGE. SEE SECTION 1510.1 FBC | | 2004. | | | | 4- LAST PAGE OF ENGINEER REPORT IS | | LISTING ALL ZONES AS ZONE 1. WHEN DOING | | CALCULATIONS FOR CORRECT NOA (SEE ITEMS | | 1 AND 2 ABOVE) MAKE SURE CORRECT ROOF | | ZONES ARE LISTED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|