Plan Review Notes
Plan Review Notes For Permit 06070722
Permit Number 06070722
Review Stop E
Sequence Number 4
Notes
Date Text
2007-05-01 12:08:16*** UNSAT 4TH REVIEW***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH
 STILL NEEDS TO BE CLARIFIED OR ADDRESSED.
 AS MANY ITEMS ON PLANS HAVE BEEN REVISED FROM THE LAST
 SET OF REVIEWED PLANS THERE ARE SEVERAL NEW COMMENTS
 WHICH ARE BASED ON THE REVISIONS MADE TO PLANS WHICH
 ARE NOT THE SAME AS PREVIOUSLY SUBMITTED PLANS. PLEASE
 SEE SOME OF THE COMMENTS ARE THE SAME FROM PREVIOUS
 REVIEW. RECORD AS SHOWN.
  
  
 1) NOTE: PLEASE SEE SOME CIRCUITS ARE MISSING FROM
 PLANS AND SOME OF THE CIRCUITING ON PLANS DOES NOT
 COORDINATE WITH THE PANEL SCHEDULE SUBMITTED. PLEASE
 SEE SOME OF THE CIRCUITS ON PANEL SCHEDULE ARE
 REPEATED.
 PLEASE SEE THAT THE USE OF GEN LTS ETC MAY NOT BE USED.
 ROOMS AND AREAS ARE TO BE SPECIFIC. PLEASE SEE THE
 FOLLOWING TEXT WHICH IS EXTRACTED FROM THE CODE.
 ** CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.**
 PLEASE SEE THAT THIS CIRCUITING SHALL CORRELATE WITH
 THE SUBMITTED PANEL SCHEDULE. 408.4, 310.16
  
  
 2) NOTE:PLEASE SEE MISSING REQUIRED DEDICATED
 CIRCUITS FOR SMALL APPLIANCE CIRCUITS AND DINING ROOM
 CIRCUITS PER 210.52B1, 210.11C1, 220.16
 THIS IS THE SAME COMMENT AS TWO SMALL APPLIANCE
 CIRCUITS ARE SHOWN HOWEVER ONLY ONE IN THE KITCHEN AND
 ONE IN THE DINING ROOM. THE KITCHEN REQUIRES TWO
 CIRCUITS AT A MINIMUM. PLEASE SEE THE DINING AREA IS
 PERMITTED TO BE ON ONE OR *MORE* OF THE SMALL APPLIANCE
 CIRCUITS.( IF MORE THAN TWO, THEN 1500VA WOULD BE
 SHOULD FOR EACH ONE OVER THE TWO MINIMUM)
  
 3) NOTE: PLEASE SEE THE MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM THE NEW J-BOX TO THE NEW PANEL. PLEASE
 ALSO NOT ON PLANS, THAT IF THE EXISTING CONDUIT FROM
 THE EXISTING METER AND MAIN DOES NOT CONTAIN AN
 EQUIPMENT GROUNDING CONDUCTOR, ONE WILL BE REQUIRED TO
 BE INSTALLED OR WORDS TO THAT EFFECT. PLEASE KNOW IF
 THE EXISTING CONDUIT GROUNDING IN THE STRUCTURE IS
 RIGID AND NOT EMT, THEN AN EXISTING PATH TO THIS J-BOX
 MAY BE ADEQUATE.
 250.24, 250.110, 250.122.
  
 4) NOTE: PLEASE CORRELATE THE ITEMS/CIRCUITS SHOWN ON
 LOAD CALCULATIONS WITH THE CIRCUITS AS SHOWN ON PANEL
 SCHEDULE.
 PLEASE SEE PANEL SCHEDULE IS MISSING THE LAUNDRY
 CIRCUIT AS SHOWN ON THE LOAD CALCULATIONS.
 PLEASE SEE THE LOAD FOR THE WATER HEATER IS SHOWN AS
 3KW ON LOAD CALCULATIONS AND THE LOAD ON THE PANEL
 SCHEDULE IS SHOWN AS 4.5 KW. PLEASE SEE THE NEXT
 COMMENT FOR WATER HEATER.
  
 5) NOTE: PLEASE SEE THE LOAD ON THE PANEL SCHEDULE AND
 LOAD CALCULATIONS BOTH WHICH ARE SHOWN AS 3KW AND 4.5KW
 EXCEED THAT OF THE CONDUCTORS, RATING OF THE BREAKER
 AND IS ONLY SHOWN AS 120V?
 PLEASE SEE 422.13 AS THE MINIMUM SIZING FOR THIS
 CIRCUIT MUST BE DONE AT 125% INCLUDING LOAD, OCP AND
 CONDUCTOR SIZES.
 PLEASE COORDINATE THE ACTUAL WATER HEATER SIZE AND GO
 FROM THERE.
  
 6) NOTE: PLEASE SEE MISSING RECEPT(S) TO BE LOCATED PER
 210.52 (SEE BEDROOM WALL)
  
 7) NOTE:THIS IS THE SAME NOTE: IF THESE ARE 110V,
 BATTERY BACK UP DEVICES WHICH ACTUALLY DETECT AND SOUND
 AN ALARM, THEN THESE ARE * SMOKE ALARMS*
 ** PREVIOUS NOTE **
 PLEASE SEE THE SMOKE DEVICE IS BEING NOTED AS 110V W/
 BATTERY BACK UP AND PLANS INDICATE UNIT AS A SD WHICH
 MEANS SMOKE DETECTOR. PLEASE SEE NFPA-72 DEFINITIONS AS
 A SMOKE DETECTOR IS IN FACT A DEVICE WHICH ONLY DETECTS
 AND IS PART OF A FIRE ALARM SYSTEM. IF THIS DEVICE IS
 INDEED A DEVICE WHICH DETECTS AND SOUNDS, THEN THIS
 DEVICE SHOULD BE SHOWN AND NOTED AS "SA" AS A SMOKE
 ALARM DEVICE.
 R313 2004 FBC, NFPA-72 2002 11.5, 11.8
 PLEASE KNOW THIS WAS PROVIDED TO THIS OFFICE FROM NFPA
 THAT NOTATION OF SD AND SA IS CLEARLY DIFFERENT AND
 SHALL BE INDICATED AS SUCH.
  
 8) NOTE: SAME NOTE, PLEASE SEE ONLY ONE CIRCUIT IS
 BEING NOTED AS BEING AFCI PROTECTED WHEN THE SMOKE
 DEVICES ALSO REQUIRE PROTECTION.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ARC FAULT PROTECTION IS BEING SHOWN FOR
 RECEPTS ONLY WHERE THE 2002 NEC REQUIRES AFCI
 PROTECTION FOR ALL BRANCH CIRCUITING IN SLEEPING ROOMS.
 PLEASE LIST CIRCUITS ON PANEL SCHEDULE.
 PANEL SCHEDULE SHOWS AFCI FOR BATH ROOM?
  
 9) NOTE:PLEASE SEE 210.4 AS THE DISHWASHER AND
 DISPOSAL ARE NOW BEING SHOWN ON THE SAME DEVICE, YET ON
 TWO DIFFERENT CIRCUITS? PLEASE SEE THE SECTION ABOVE AS
 IF BOTH ARE ON THE SAME DEVICE/YOKE, THEN THIS WOULD BE
 REQUIRED TO BE A 2-POLE BREAKER. PLEASE REVISE PANEL.
  
 10) NOTE: PLEASE SEE THE NEW BATH CIRCUIT WHICH IS
 NOTED ON PANEL SCHEDULE INDICATES A LOAD OF 5KW. PLEASE
 CLARIFY HOW THIS IS POSSIBLE?
 PLEASE ALSO SEE THIS SAME BATH CIRCUIT IS BEING NOTED
 AND SHOWN FEEDING THE LIVING ROOM RECEPTACLES WHICH IS
 NOT PERMITTED.
 PLEASE SEE 210.52D, 210.11C3 AS BATH GFI MAY NOT FEED
 OTHER AREAS, ONLY THE BATH.
  
 11) NOTE: PLEASE SEE THE OCCUPANCY IS NOTED AS
 *ANCILLARY/MAIL ROOM*?
 THE R-2 APPEARS TO BE CORRECT HOWEVER NOT SURE WHERE A
 MAIL ROOM COMES INTO AFFECT.?
 FBC 106.1.2
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  