Plan Review Notes
Plan Review Notes For Permit 06070722
Permit Number 06070722
Review Stop E
Sequence Number 3
Notes
Date Text
2006-12-17 11:24:21*** UNSAT 3RD REVIEW***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH
 STILL NEEDS TO BE CLARIFIED OR ADDRESSED.
 THIS IS ACTUALLY THEFIRST SET OF PLANS BEING
 SUBMITTED FOR REVIEW UNDER THE THE NEW DESIGNER OF
 RECORD AS SHOWN.
  
 ** PLEASE SEE PREVIOUS REVIEWS WHICH REQUESTED PLANS
 FOR REVIEW FOR SCOPE OF WORK BEING PERFORMED. PLEASE
 SEE THE COMMENTS BELOW ARE BASED ON THE PLANS
 SUBMITTED.
  
 1) NOTE: PLEASE SEE PLANS MISSING CIRCUITING AS
 PREVIOUSLY REQUESTED. PLEASE SEE THAT THIS CIRCUITING
 SHALL CORRELATE WITH THE SUBMITTED PANEL SCHEDULE.
 408.4, 310.16
  
 2) NOTE: PLEASE SEE MISSING REQUIRED DEDICATED CIRCUITS
 FOR SMALL APPLIANCE CIRCUITS AND DINING ROOM CIRCUITS
 PER 210.52B1, 210.11C1, 220.16
  
 3) NOTE: PLEASE SEE EXISTING PANEL IS BEING SHOWN
 LOCATED SO THAT THE MINIMUM CLEARANCE IS NOT MET IN
 110.26. PLEASE SEE NOTE ON PLANS MENTIONS THIS IS
 EXEMPT DUE TO INSPECTOR AND IS "GRANDFATHERED" PLEASE
 KNOW MINIMUM CLEARANCES IN THE CODE HAVE GONE BACK
 FURTHER THAN WHEN THIS BUILDING WAS CONSTRUCTED AND A
 LIFE SAFETY CODE HAZARD IS NOT "GRANDFATHERED" AS
 STATED ON PLANS. PLEASE KNOW THIS LICENSED PLANS
 EXAMINER WILL NOT MAKE ANY EXCEPTION TO THIS. PLEASE
 SEE 110.26, PLEASE RELOCATE AND MEET CODE OR PROVIDE
 DOCUMENTATION TO THE INSPECTOR WHICH WILL BE REQUIRED
 TO BE THE CHIEF ELECTRICAL INSPECTOR AND THE BUILDING
 OFFICIAL FOR ANY EXCEPTIONS.
 THIS REVIEWER WILL RELEASE PROJECT AT THAT TIME IF THIS
 EXCEPTION IS GRANTED AND NEW LICENSED PLANS EXAMINER/
 INSPECTOR OR BUILDING OFFICAL WILL TAKE OVER REVIEWING
 AND SIGNING OFF OF CODE COMPLIANCE.
  
 4) NOTE: PLEASE SEE MISSING COUNTER SPACE GFI LOCATIONS
 AS REQUIRED PER 210.52C1
  
 5) NOTE: PLEASE SEE MISSING RECEPTS TO BE LOCATED PER
 210.52
  
 6) NOTE: PLEASE SEE THE SMOKE DEVICE IS BEING NOTED AS
 110V W/ BATTERY BACK UP AND PLANS INDICATE UNIT AS A SD
 WHICH MEANS SMOKE DETECTOR. PLEASE SEE NFPA-72
 DEFINITIONS AS A SMOKE DETECTOR IS IN FACT A DEVICE
 WHICH ONLY DETECTS AND IS PART OF A FIRE ALARM SYSTEM.
 IF THIS DEVICE IS INDEED A DEVICE WHICH DETECTS AND
 SOUNDS, THEN THIS DEVICE SHOULD BE SHOWN AND NOTED AS
 "SA" AS A SMOKE ALARM DEVICE.
 PLEASE KNOW THIS WAS PROVIDED TO THIS OFFICE FROM NFPA
 THAT NOTATION OF SD AND SA IS CLEARLY DIFFERENT AND
 SHALL BE INDICATED AS SUCH.
  
 7) NOTE: PLEASE SEE ARC FAULT PROTECTION IS BEING SHOWN
 FOR RECEPTS ONLY WHERE THE 2002 NEC REQUIRES AFCI
 PROTECTION FOR ALL BRANCH CIRCUITING IN SLEEPING ROOMS.
 PLEASE LIST CIRCUITS ON PANEL SCHEDULE.
 PANEL SCHEDULE SHOWS AFCI FOR BATH ROOM?
  
 8) NOTE: PLEASE SEE PLANS REFER TO A 2004 NEC. PLEASE
 KNOW AS THIS PROJECT CAME IN BEFORE THE CODE CHANGE
 THIS SHOULD BE SHOWN AS THE 2002.
 ** PLEASE KNOW THE NEXT CODE FOR THE NEC AFTER THE 2002
 WILL BE THE 2005 NEC WHICH WAS ADOPTED ON 12/8/06. THIS
 PROJECT IS UNDER THE 2002.
  
 9) NOTE: PLEASE SEE NOTICE OF COMMENCMENT STILL BEING
 SUBMITTED HAS EXPIRED AND HAS BECOME VOID . PLEASE SEE
 FLORIDA STATUTES 713.13(2). WHEN WORK HAS NOT COMMENCED
 WITHIN 90 DAYS OF RECORDING SUCH NOTICE OF
 COMMENCEMENT, THE NOC SHALL BEOMCE VOID. THIS WAS
 RECORDED IN JULY OF 06, A NEW RECORDED NOC WIL BE
 REQUIRED BEFORE PICKIGN UP PERMIT.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.