2006-12-17 11:24:21 | *** UNSAT 3RD REVIEW*** |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH |
| STILL NEEDS TO BE CLARIFIED OR ADDRESSED. |
| THIS IS ACTUALLY THEFIRST SET OF PLANS BEING |
| SUBMITTED FOR REVIEW UNDER THE THE NEW DESIGNER OF |
| RECORD AS SHOWN. |
| |
| ** PLEASE SEE PREVIOUS REVIEWS WHICH REQUESTED PLANS |
| FOR REVIEW FOR SCOPE OF WORK BEING PERFORMED. PLEASE |
| SEE THE COMMENTS BELOW ARE BASED ON THE PLANS |
| SUBMITTED. |
| |
| 1) NOTE: PLEASE SEE PLANS MISSING CIRCUITING AS |
| PREVIOUSLY REQUESTED. PLEASE SEE THAT THIS CIRCUITING |
| SHALL CORRELATE WITH THE SUBMITTED PANEL SCHEDULE. |
| 408.4, 310.16 |
| |
| 2) NOTE: PLEASE SEE MISSING REQUIRED DEDICATED CIRCUITS |
| FOR SMALL APPLIANCE CIRCUITS AND DINING ROOM CIRCUITS |
| PER 210.52B1, 210.11C1, 220.16 |
| |
| 3) NOTE: PLEASE SEE EXISTING PANEL IS BEING SHOWN |
| LOCATED SO THAT THE MINIMUM CLEARANCE IS NOT MET IN |
| 110.26. PLEASE SEE NOTE ON PLANS MENTIONS THIS IS |
| EXEMPT DUE TO INSPECTOR AND IS "GRANDFATHERED" PLEASE |
| KNOW MINIMUM CLEARANCES IN THE CODE HAVE GONE BACK |
| FURTHER THAN WHEN THIS BUILDING WAS CONSTRUCTED AND A |
| LIFE SAFETY CODE HAZARD IS NOT "GRANDFATHERED" AS |
| STATED ON PLANS. PLEASE KNOW THIS LICENSED PLANS |
| EXAMINER WILL NOT MAKE ANY EXCEPTION TO THIS. PLEASE |
| SEE 110.26, PLEASE RELOCATE AND MEET CODE OR PROVIDE |
| DOCUMENTATION TO THE INSPECTOR WHICH WILL BE REQUIRED |
| TO BE THE CHIEF ELECTRICAL INSPECTOR AND THE BUILDING |
| OFFICIAL FOR ANY EXCEPTIONS. |
| THIS REVIEWER WILL RELEASE PROJECT AT THAT TIME IF THIS |
| EXCEPTION IS GRANTED AND NEW LICENSED PLANS EXAMINER/ |
| INSPECTOR OR BUILDING OFFICAL WILL TAKE OVER REVIEWING |
| AND SIGNING OFF OF CODE COMPLIANCE. |
| |
| 4) NOTE: PLEASE SEE MISSING COUNTER SPACE GFI LOCATIONS |
| AS REQUIRED PER 210.52C1 |
| |
| 5) NOTE: PLEASE SEE MISSING RECEPTS TO BE LOCATED PER |
| 210.52 |
| |
| 6) NOTE: PLEASE SEE THE SMOKE DEVICE IS BEING NOTED AS |
| 110V W/ BATTERY BACK UP AND PLANS INDICATE UNIT AS A SD |
| WHICH MEANS SMOKE DETECTOR. PLEASE SEE NFPA-72 |
| DEFINITIONS AS A SMOKE DETECTOR IS IN FACT A DEVICE |
| WHICH ONLY DETECTS AND IS PART OF A FIRE ALARM SYSTEM. |
| IF THIS DEVICE IS INDEED A DEVICE WHICH DETECTS AND |
| SOUNDS, THEN THIS DEVICE SHOULD BE SHOWN AND NOTED AS |
| "SA" AS A SMOKE ALARM DEVICE. |
| PLEASE KNOW THIS WAS PROVIDED TO THIS OFFICE FROM NFPA |
| THAT NOTATION OF SD AND SA IS CLEARLY DIFFERENT AND |
| SHALL BE INDICATED AS SUCH. |
| |
| 7) NOTE: PLEASE SEE ARC FAULT PROTECTION IS BEING SHOWN |
| FOR RECEPTS ONLY WHERE THE 2002 NEC REQUIRES AFCI |
| PROTECTION FOR ALL BRANCH CIRCUITING IN SLEEPING ROOMS. |
| PLEASE LIST CIRCUITS ON PANEL SCHEDULE. |
| PANEL SCHEDULE SHOWS AFCI FOR BATH ROOM? |
| |
| 8) NOTE: PLEASE SEE PLANS REFER TO A 2004 NEC. PLEASE |
| KNOW AS THIS PROJECT CAME IN BEFORE THE CODE CHANGE |
| THIS SHOULD BE SHOWN AS THE 2002. |
| ** PLEASE KNOW THE NEXT CODE FOR THE NEC AFTER THE 2002 |
| WILL BE THE 2005 NEC WHICH WAS ADOPTED ON 12/8/06. THIS |
| PROJECT IS UNDER THE 2002. |
| |
| 9) NOTE: PLEASE SEE NOTICE OF COMMENCMENT STILL BEING |
| SUBMITTED HAS EXPIRED AND HAS BECOME VOID . PLEASE SEE |
| FLORIDA STATUTES 713.13(2). WHEN WORK HAS NOT COMMENCED |
| WITHIN 90 DAYS OF RECORDING SUCH NOTICE OF |
| COMMENCEMENT, THE NOC SHALL BEOMCE VOID. THIS WAS |
| RECORDED IN JULY OF 06, A NEW RECORDED NOC WIL BE |
| REQUIRED BEFORE PICKIGN UP PERMIT. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |