2006-09-14 00:00:00 | **** UNSAT2ND REVIEW ***** |
| |
| |
| ** PLEASE SEE COMMENTS FROM PREVIOUS |
| REVIEW. |
| AS REQUESTED ON PREVIOUS REVIEW , PLANS |
| CAN NOT BE DONE BY A DRAFTING/ DESIGN |
| CO. |
| NOTES BELOW ARE TAKEN DIRECTLY FROM |
| PREVIOUS REVIEW. |
| |
| |
| 1) NOTE: NO. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SUBMIT ARCHITECTURAL |
| PLANS DONE BY AN ARCHITECT PER FS |
| 481.229. |
| PLEASE SHOW CODE COMPLIANCE FOR ALL |
| ELECTRCAIL IN SCOPE OF WORK. PLEASE ALSO |
| SEE NFPA-72 11.5.1.1,11.8.3 FOR REQUIRED |
| SD'S. R313 |
| PLEASE SHOW ALL ELECTRICAL DEVICES AS |
| REQUIRED ALONG WTIH CIRCUITING ON PLANS. |
| PLEASE CORRELATE WITH PANEL SCHEDULE (S) |
| TO BE SUBMITTED. PLEASE SHOW ALL |
| REQUIRED DEDICATED CIRCUITS. |
| |
| ** PLEASE SEE NFPA-70 2002 |
| 210.52,210.11C1,C2,C3, 210.52C1-5, |
| 210.52D, 220.16, 220.31, 215.5, 240.24, |
| 408.16, 110.26, 210.70, 240.4,310.16 ETC |
| ETC. |
| |
| |
| |
| ****NEW NOTE ** |
| |
| 2) NOTE: PLEASE SEE FS 553.80(2)(B). |
| THIS IS A NOTICE GIVEN AT THIS TIME. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |