Plan Review Notes For Permit 06070699
Permit Number 06070699
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-16 00:00:00** UNSAT **
  
 1) NOTE: PLEASE PROVIDE LOAD ON EXISTING
 PANEL AND LOAD BEING INCREASED.
 PLEASE LABEL THE LOADS INTENDED FOR NEW
 RECEPTS.
 220, 215.5, 408.4
  
 2) NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS THES OUTLETS BEING ADDED IN
 "IT" RM, PLEASE CLARIFY IF THIS PANEL
 CONTAINS THE REQUIRED "SHUNT/DISCONNECT
 DEVICE AS REQUIRED UNDER 645.10
 THESE MUST BE FED FROM THE SAME PANEL
 WHICH FEEDS OTHER ELECTRICAL IN THE SAME
 RM. ETC
  
 3) NOTE: PLEASE CLARIFY THE M/C 10/2
 SHOWN THAT THIS ALSO CONTAINS AN
 "EQUIPMENT GROUNDING CONDUCTOR".
 250.110,250.122
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  