2008-06-04 18:11:36DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 1. SHT P3 VENT FOR FIXTURE MG07 NOT APPROVED. VENT
 SHALL NOT OFFSET HORIZONTALLY UNTILL 6" ABOVE THE FLOOD
 RIM LEVEL OF THE FLOOR SINK. SECTION 905.4.
  
 2. SHT P3 VENT FOR FLOOR SINK SHALL CONNECT ABOVE THE
 CENTERLINE OF THE HORIZONTAL DRAIN PIPE. SECTION 905.3.
 (FLOOR SINK BY COL. LINE 6/E-D.
  