2008-01-23 14:32:26REVISION 3 PG M2: DENIED
  
 NOTE: A FOUR PAGE SCOPE-OF-WORK REPORT WAS PROVIDED TO
 SHOW NATURE AND LOCATION OF CHANGES. THIS REPORT DOES
 NOT INDICATE ANY MECHANICAL PLANS AS PART OF THIS
 REVISION. HOWEVER, PAGES M1, M2, R1, R2 AND R3 ARE ALL
 INCLUDED IN THIS REVISION.
  
 1. PG M2: ROOFTOP UNIT SCHEDULE HAS BEEN REVISED TO
 REFLECT THE NEW OWNER-SUPPLIED EQUIPMENT. IN
 CONJUNCTION WITH THAT CHANGE, NOTE #9 HAS BEEN UPDATED
 TO REFLECT THE EFFICIENCY RATINGS OF THE NEWLY
 SPECIFIED EQUIPMENT. THE EFFICIENCIES LISTED IN THIS
 NOTE DO NOT CORRESPOND WITH THE CURRENT PERMIT ENERGY
 CALCULATIONS. IN MOST CASES, THE EFFICIENCIES HAVE GONE
 DOWN. PROVIDE REVISED ENERGY CALCULATIONS WHICH
 INCORPORATE THE NEW EQUIPMENT EFFICIENCIES.
  
 2. PG M2: THE 5 TON UNIT SHOWS AN EFFICIENCY RATING OF
 12.6 SEER. THE MINIMUM EFFICIENCY REQUIRED FOR A UNIT
 THIS SIZE IS 13.0 SEER IN ACCORDANCE WITH FBC TABLE
 13-407.1.ABC.3.2A. THIS IS A PRESCRIPTIVE MINIMUM
 REGARDLESS OF WHAT PASSES ON THE CALCULATIONS IN
 ACCORDANCE WITH FBC 13-400.1. PG M2 WILL NOT PASS
 REVIEW UNTIL THE NEW INFORMATION IS COORDINATED WITH
 REVISED ENERGY CALCULATIONS.
  