Date |
Text |
2007-07-30 10:18:13 | 6901 OKEECHOBEE BLVD. / 06070683 |
| BUILDING PROVISOS: |
| |
| 1) ROOFING PERMIT TO BE A SEPARATE PERMIT WITH |
| ASSOCIATED FEES AND REVIEW, NOTE THE HIGHLIGHTED |
| SUBSYSTEM REQUIRES ENHANCED FASTENING. |
| THE SYSTEM PROVIDED STATESLIMITATION# 7, SHOULD |
| THE FASTENERRESISTANCE BE LESS THAN THAT REQUIRED, |
| AS DETERMINED BY THEBUILDING OFFICIAL, A REVISED |
| FASTENER SPACING, PREPARED , SIGNEDAND SEALED BY A |
| FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED |
| ARCHITECT ORREGISTERED ROOF CONSULTANT MAY BE |
| SUBMITTED. PLEASE PROVIDE THE RAS 117 CALCULATIONS FOR |
| ROOFING SUB-PERMIT. |
| |
| 2) RULE 9B-72 REQUIRES TESTING FOR ROOF ACCESS HATCHES, |
| CURRENTLY THERE ARE NO ROOF HATCHES THAT HAVE APPLIED |
| FOR STATE APPROVAL. BEFORE A CERTIFICATE OF COMPLETION |
| WILL BE ISSUED, THE CONTRACTOR SHALL EITHER OBTAIN A |
| PRODUCT APPROVAL THROUGH THE STATE WEBSITE THAT WILL |
| MEET THE |
| WIND PRESSURES OR APPLY AND RECEIVE LOCAL PRODUCT |
| APPROVAL WITHIN THIS JURISDICTION. THE CITY OF WEST |
| PALM BEACH HAS THE SAME 10 CRITERIA AS THE STATE |
| APPROVAL INCLUSIVE OF THIRD PARTY QUALITY ASSURANCE |
| PROGRAM, WITH THE THIRD PARTY BEING APPROVED THROUGH |
| THE STATE. |
| |
| 3)109.3.10.1 HURRICANE PROTECTION. IT SHALL BE |
| UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| DAMAGE TO PERSONS OR PROPERTY FROM HIGH |
| WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR |
| SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS |
| WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED |
| SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN |
| ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO |
| VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE |
| PURSUANT TO SECTION 113 OF THIS CHAPTER. |