Date |
Text |
2008-02-04 15:53:18 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| |
| 1. SHT P1 INDICATES THAT EWC-1 IS DELETED. SHT C1 |
| PLUMBING FIXTURE COUNT INDICATES THAT 2 DRINKING |
| FOUNTAINS ARE REQUIRED. DELETING 1 DRINKING FOUNTAIN |
| ONLY LEAVES 1 DRINKING FOUNTAIN. THIS DOES NOT COMPLY |
| WITH TABLE 403.1. PLEASE CLARIFY. |
| |
| 2. SHT P2 INDICATES THE WATER SUPPLY FOR THE DRINKING |
| FOUNTAIN EWC-1 HAS BEEN DELETED. THIS IS REQUIRED PER |
| TABLE 403.1. PLEASE CLARIFY. |
| |
| 3. SHT P3 THE WATER RISER DIAGRAM AND THE SANITARY |
| RISER DIAGRAM SHOWS THE SANITARY AND WATER HAVE BEEN |
| DELETED FOR EWC-1 (DRINKING FOUNTAIN). THIS IS REQUIRED |
| PER TABLE 403.1. PLEASE CLARIFY. |
| |
| 4. SHT P3 SANITARY RISER DIAGRAM SHOWS A DRY HORIZONTAL |
| VENT FOR THE FLOOR SINK WITH A VENT AT FIXTURE R32: |
| REACH IN FROZEN. SECTION 905.3. PLEASE SHOW |
| COMPLIANCE. |
| |
| 5. SHT P3 SANITARY RISER DIAGRAM DOES NOT REFLECT THE |
| CHANGES SHOWN ON SHT P1 AT THE GREASE INTERCEPTORS. |
| SECTION 106.1.1 AND SECTION 901.2.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |