Plan Review Notes
Plan Review Notes For Permit 06070683
Permit Number 06070683
Review Stop P
Sequence Number 5
Notes
Date Text
2008-02-04 15:53:18DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 1. SHT P1 INDICATES THAT EWC-1 IS DELETED. SHT C1
 PLUMBING FIXTURE COUNT INDICATES THAT 2 DRINKING
 FOUNTAINS ARE REQUIRED. DELETING 1 DRINKING FOUNTAIN
 ONLY LEAVES 1 DRINKING FOUNTAIN. THIS DOES NOT COMPLY
 WITH TABLE 403.1. PLEASE CLARIFY.
  
 2. SHT P2 INDICATES THE WATER SUPPLY FOR THE DRINKING
 FOUNTAIN EWC-1 HAS BEEN DELETED. THIS IS REQUIRED PER
 TABLE 403.1. PLEASE CLARIFY.
  
 3. SHT P3 THE WATER RISER DIAGRAM AND THE SANITARY
 RISER DIAGRAM SHOWS THE SANITARY AND WATER HAVE BEEN
 DELETED FOR EWC-1 (DRINKING FOUNTAIN). THIS IS REQUIRED
 PER TABLE 403.1. PLEASE CLARIFY.
  
 4. SHT P3 SANITARY RISER DIAGRAM SHOWS A DRY HORIZONTAL
 VENT FOR THE FLOOR SINK WITH A VENT AT FIXTURE R32:
 REACH IN FROZEN. SECTION 905.3. PLEASE SHOW
 COMPLIANCE.
  
 5. SHT P3 SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 CHANGES SHOWN ON SHT P1 AT THE GREASE INTERCEPTORS.
 SECTION 106.1.1 AND SECTION 901.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved