Plan Review Notes
Plan Review Notes For Permit 06070683
Permit Number 06070683
Review Stop E
Sequence Number 5
Notes
Date Text
2007-07-10 11:56:192007-07-10 11:56:19
  
 **** UNSAT 6THREVIEW ****
  
 ** THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION.
  
  
 1) NOTE: PLEASE SEE THERE ARE SOME ITEMS ON THE ENERGY
 CALCULATIONS WHICH DO NOT CORRELATE WITH PLANS. PLEASE
 KNOW THAT THIS IS THE FIRST REVIEW OF THE INPUT DATA
 REPORT AS IT WAS NOT SUBMITTED ON THE LAST REVIEW. THIS
 WAS NOTED ON PREVIOUS REVIEW.
 PLEASE BE SURE ALL AREAS WHICH ARE DESIGNATED ON PLANS
 ARE THAT OF THE SAME AREAS AS DESIGNATED ON THE ENERGY
 CALCULATIONS. PLEASE SEE SOME OF THESE AREAS ARE
 MISSING AND/OR DO NOT COORDINATE AT THIS TIME. PLEASE
 SEE IT IS NOT POSSIBLE FOR THE METHOD OF CONTROL FOR
 LIGHTING TO BE SHOWN AS *MANUAL ON/OFF* WHEN THE
 LIGHTING ON PLANS AND AS REQUIRED UNDER CHAPTER 13 OF
 THE FBC REQUIRES LIGHTING TO BE AUTOMATED.
 PLEASE SEE SOME SEPARATE SPACES STILL DO NOT INDICATE
 OVER RIDE DEVICES. PLEASE SEE 13-415.1.ABC1.2 AS THESE
 AREAS SHALL CONTAIN EITHER OF THE CONTROLS AS SET-FORTH
 HOWEVER MAY NOT ONLY CONTAIN A SINGLE POLE OR THREE-WAY
 SWITCH. THE DEVICE MUST BE CAPABLE OF OVER RIDING THE
 TIMED SCHEDULING WHEN ON THE TIMED SCHEDULE SYSTEM. IF
 AN AREA IS NOT ON THE SCHEDULED TIMER CONTROLS OR
 ENERGY MANAGEMENT SYSTEM THEM SEPARATE DEVICES SUCH AS
 OS TYPE DEVICES ARE PERMITTED.
 PLEASE SEE AREAS WHICH DO NOT CONTAIN OVER RIDE
 CONTROLS FOR EXAMPLE: PHARMACY, FAMILY TOILET ROOM (NO
 CONTROLS) , LIGHTING OUTSIDE OF TOILETS, ETC PLEASE SEE
 LIGHTS OUTSIDE OF THESE SAME ROOMS AND OTHER AREAS.
 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 2) NOTE: PLEASE SEE THE COVER SHEET C1 STILL INDICATES
 THE WRONG CODE FOR ELECTRICAL.. ALL OF THE PREVIOUS
 REVIEW STATED THE CODES WHICH NEEDED TO BE ON PLANS.
 PLEASE SEE THE PLANS STILL INDICATE THE 2002
 NEC/NFPA-70. THIS SHOULD BE THE 2005 NEC/ NFPA-70. THIS
 CAN BE REDLINED.
  
 3) NOTE: PLEASE KNOW THAT IT MAY BE POSSIBLE PENDING
 OTHER TRADE REVIEWS TO PROVIDE WHAT IS KNOWN AS A
 *PROVISO* FOR THE LIGHTING CONTROL PART OF THE COMMENT
 ABOVE AND COMMENT NUMBER 2.
 THE *PROVISO* WOULD SET-FORTH CONDITIONS THAT THE
 PERMIT CAN BE ISSUED AND THE LIGHTING CONTROLS ON PLANS
 WOULD NEED TO BE ADDRESSED AND SUBMIT REVISED
 ELECTRICAL PLANS WITHIN 30DAYS OF PERMIT ISSUANCE.
 PLEASE KNOW HOWEVER THAT THE ENERGY CALCULATIONS MAY
 NOT BE DONE AS A *PROVISO* AND MUST BE ADDRESSED AT
 THIS TIME.
 PLEASE BE SURE ANY REVISED ENERGY CALCULATIONS WILL BE
 REQUIRED TO CONTAIN ALL SIGNATURES FROM THE RESPONSIBLE
 PERSONS OF RECORD INCLUDING THAT OF THE OWNER AGENT.
 13-103.1.1.1
 *** IMPORTANT , THE REVIEW FROM THE MECHANICAL REVIEWER
 HAS NOT YET BEEN DONE FOR THE ENERGY CALCULATIONS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-09 20:06:072007-07-09 20:06:07
 PLANS REMOVED FROM INCOMING FOR ELECTRICAL REVIEW.
 PLANS WILL BE RETURNED TO INCOMING WAITING FOR COMM
 BOARD ONCE ELECTRICAL REVIEW IS COMPLETED.