2007-06-10 14:07:49** UNSAT 4TH REVIEW **
  
  
  
 ********** WAL-MART BUILD -OUT******
  
 1) NOTE:PLEASE SEE PLANS ARE STILL ONLY SUBMITTED FOR
 "PLAN REVIEW" AND HAVE NOT BEEN SUBMITTED FOR PERMIT.
 EVEN WHEN PLANS ARE 100% CODE COMPLIANT, THE REVIEW
 WILL STILL BE IN FAILED STATUTES AS THE REVIEW OF
 PERMIT APPLICATION(S), LICENSING ETC WILL STILL TAKE
 PLACE.
  
 2) NOTE: PLEASE SUBMIT ONLY DOCUMENTS RELEVANT TO
 PROJECT AND SCOPE OF WORK. PLEASE SEE THE SUBMITTED
 PACKAGE CONTAINS NUMEROUS DOCUMENTS WHICH ARE NOT
 RELEVANT OR NO LONGER RELEVANT TO SCOPE OF WORK OR DOES
 NOT NEED TO BE IN PACKAGE. PLEASE KNOW THAT PRINTING
 OUT OF ON-LINE NOTES DOES NOT NEED TO PLACED IN PACKAGE
 FOR OUR REVIEW AS WE ALREADY HAVE THE NOTES, SEVERAL OF
 THESE WERE SUBMITTED.
 FBC 106.3
  
 3) NOTE: PLEASE SEE EFP SHEETS WHICH ARE NOT SEALED AS
 REQUIRED PER FAC 61G15-23.001.
 PLEASE SEE FS471.025
 ** THIS IS REQUIRE WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 4) NOTE: PLEASE SEE MISSING REQUIRED LICENSE
 INFORMATION ON TITLE BLOCKS FOR EFP SHEETS. PLEASE SEE
 FS 471.023 WHICH REQUIRES A CERTIFICATE OF
 AUTHORIZATION NUMBER AND TO BE PLACED ON TITLE BLOCKS.
 THIS IS FOR SACRAMENTO ENGINEERING.
 **THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 5) NOTE: THIS IS THE SAME COMMENT AS PREVIOUS REVIEW AS
 THE PLANS WERE NOT CHANGED. PLEASE SEE THE A SHEETS
 STILL INDICATE TWO CODES. THE FA/EFP SHEETS INDICATE
 CODES NOT UNDER THE FBC. (IBC,IFC )
  
 **PREVIOUS REVIEW NOTE**
 PLEASE SEE THE PREVIOUS REVIEWS WHICH MENTIONED THE
 CODES REQUIRED DEPENDING ON WHEN PERMIT APPLICATION IS
 MADE. PLEASE SEE THE PLANS NOW LIST BOTH CODES FOR 2005
 AND 2002 ARE BEING SHOWN ON PLANS FOR DESIGN ETC??
 PLEASE MAKE THE CORRECTIONS.
 PLEASE SEE THE 2005 NFPA-70 AND THE 2004 FBC REVISIONS
 #6 WILL BE REQUIRED.
 PLEASE SEE NUMEROUS SECTIONS OF THE FIRE SHEETS WHICH
 SPECIFY THE 1996 NFPA-72 AND OTHER CODES NOT ADOPTED
 UNDER THE STATE. PLEASE SEE ALL OF THE NEW CODES
 ADOPTED IN THE REFERENCE TABLES AND CORRECT PLANS.
  
 6) NOTE:PLEASE SEE THE NOTES WITH RESPECT TO FBC
 CHAPTER 13 REMAIN IN AFFECT.
 PLEASE SEE THE ENERGY CALCULATIONS ARE NOT PER
 13-415.1.AB.1.1. PLEASE SEE THE PROGRAM OF FLA-COM
 VERSION 3.0 IS THE LATEST EDITION ADOPTED BY THE STATE
 AND CHAPTER 13.
 WHEN THESE ARE DONE, THE ENERGY CALCULATIONS MUST ALSO
 CONTAIN THE INPUT DATA REPORT TO COINCIDE WITH THE
 PLANS FOR REVIEW.
 PLEASE SEE THESE WILL BE REQUIRED TO BE SIGNED, DATED
 AND SEALED AS PREVIOUSLY NOTED. THE FLA-COM SHEETS HAVE
 SPACE FOR THIS.
 PLEASE SEE NOT ALL SEPARATE SPACES WHICH CONTAIN FLOOR
 TO CEILING HEIGHT PARTITIONS CONTAIN CONTROLS AS
 REQUIRED PER 13-415.1.ABC.1.1, .1.2.
 PLEASE SEE SYMBOL LEGEND DOES NOT STATE TIMES OF
 DEVICES.
 PLEASE COORDINATE ALL DOCUMENTS.
 RESPONSE FROM DESIGNER ONLY RESPONDED TO ONE OF THE
 COMMENTS MADE IN THIS NOTE FROM PREVIOUS REVIEW.
  
 ** PREVIOUS REVIEW NOTES**
 PLEASE SEE THAT THE ENERGY CALCULATIONS SUBMITTED ARE
 STILL NOT SIGNED, DATED AND SEALED BY THE DESIGNER OF
 RECORD NOR ARE THEY UNDER THE CORRECT CODE. THEY ARE
 DONE AND SUBMITTED UNDER THE 2001 IEC WHICH IS NOT IN
 EFFECT IN THE STATE OF FLORIDA. PLEASE SEE BOTH
 PREVIOUS REVIEWS WHICH MENTION TO SEE 13-415.1.AB.1.1,
 13-415.2 AND 13-103.1.1.1.
 REVIEW FOR COMPLIANCE OF CHAPTER 13 CAN NOT BE DONE AT
 THIS TIME. PLEASE ALSO SEE THAT UNDER THE 2006
 REVISIONS TO THE 2004 FBC CONTAINS CHANGES TO CHAPTER
 13.
 PLEASE SEE PREVIOUS NOTE FOR DEVICES ON RESTROOMS,
 WHICH IS NOT CLEAR WHETHER OR NOT THEY CONTAIN
 COVERAGE. PLEASE SPECIFY THE TYPE OF DEVICES. PLEASE
 SEE NOT INFORMATION IS SPECIFIED FOR MAXIMUM TIMES ON
 OVER RIDE OF THESE DEVICES AND OTHER SYSTEMS, TIME
 SCHEDULING ETC.
 PLEASE SUBMIT COMPLETED PLANS FOR COMPLIANCE WITH
 CHAPTER 13.
  
 PLEASE SEE 2004 FBC W/ 2006 REVISIONS CHAPTER 13.
 PLEASE SEE 13-413.1ABC.1, PROVIDE WORST CASE FOR
 FEEDERS AND BRANCH CIRCUITS.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3.
 PLEASE PROVIDE LIGHTING CONTROL/ ENERGY MANG SYSTEM
 DETAILS.
 PLEASE SEE 13-415.1.AB.1, 13-415.2.ABC.1 FOR TABLES
 415.2.C.1 AND 415.2.B.1.
 PLEASE ALSO BE SURE ALL ENERGY CALCULATIONS ARE SIGNED,
 DATED AND SEALED BY THE DESIGNER(S) OF RECORD.
  
 7) NOTE:PLEASE SEE THIS WAS THE NOTE FROM PREVIOUS
 REVIEW. THIS REMAINS, AS ONLY SOME SHEETS WERE REVISED
 TO CHANGE DOOR SWING. PLEASE SEE SHEETS WHICH WERE NOT
 REVISED STILL INDICATE INWARD SWING ON DOOR.
 ** PREVIOUS REVIEW NOTE **
 THIS IS TAKEN FROM PREVIOUS REVIEW AS NO CHANGES TO
 ROOM LAYOUT OR DOOR HAS BEEN MADE. PLEASE SEE THE MAIN
 ELECTRICAL ROOM SHALL CONTAIN A CLEAR AND UNOBSTRUCTED
 PATH WHICH IT DOES NOT. THERE IS A WALL CLEARLY SHOWN
 WHICH WOULD IMPEDE THE EGRESS OUT OF THE ROOM IN AN
 EMERGENCY. IN THE CASE OF FIRE OR BLINDNESS, AN
 ELECTRICIAN OR OTHER PERSON COULD BECOME TRAPPED AND
 THIS SCENARIO CREATES A LIFE SAFETY ISSUE WHICH IS NOT
 ACCEPTABLE TO THIS AHJ. PLEASE ALSO SEE THAT THE DOOR
 WILL BE REQUIRED TO OPEN OUTWARD AND WILL BE REQUIRED
 TO CONTAIN PANIC HARDWARE.
 110.26, 90.4
  
 8) NOTE: PLEASE SHOW ALL STROBES/HORN DEVICES NEW OR
 EXISTING MEETING THE 2004 FBC CHAPTER 11. 11-4.28.1,
 .2, AND .3(4).
 PLEASE SEE NOTE ABOVE WITH RESPECT TO NUMEROUS CODES
 AND SECTIONS BEING REFERENCE ON THE FIRE PROTECTION
 SHEETS WHICH ARE FROM TWO CODE CYCLES AGO.
 PLEASE ALSO KNOW THAT WE ARE ALSO CURRENTLY UNDER THE
 2002 NFPA-72
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]