Date |
Text |
2007-06-10 14:07:49 | ** UNSAT 4TH REVIEW ** |
| |
| |
| |
| ********** WAL-MART BUILD -OUT****** |
| |
| 1) NOTE:PLEASE SEE PLANS ARE STILL ONLY SUBMITTED FOR |
| "PLAN REVIEW" AND HAVE NOT BEEN SUBMITTED FOR PERMIT. |
| EVEN WHEN PLANS ARE 100% CODE COMPLIANT, THE REVIEW |
| WILL STILL BE IN FAILED STATUTES AS THE REVIEW OF |
| PERMIT APPLICATION(S), LICENSING ETC WILL STILL TAKE |
| PLACE. |
| |
| 2) NOTE: PLEASE SUBMIT ONLY DOCUMENTS RELEVANT TO |
| PROJECT AND SCOPE OF WORK. PLEASE SEE THE SUBMITTED |
| PACKAGE CONTAINS NUMEROUS DOCUMENTS WHICH ARE NOT |
| RELEVANT OR NO LONGER RELEVANT TO SCOPE OF WORK OR DOES |
| NOT NEED TO BE IN PACKAGE. PLEASE KNOW THAT PRINTING |
| OUT OF ON-LINE NOTES DOES NOT NEED TO PLACED IN PACKAGE |
| FOR OUR REVIEW AS WE ALREADY HAVE THE NOTES, SEVERAL OF |
| THESE WERE SUBMITTED. |
| FBC 106.3 |
| |
| 3) NOTE: PLEASE SEE EFP SHEETS WHICH ARE NOT SEALED AS |
| REQUIRED PER FAC 61G15-23.001. |
| PLEASE SEE FS471.025 |
| ** THIS IS REQUIRE WHETHER OR NOT COMMENT IS MADE BY |
| OTHER TRADES. |
| |
| 4) NOTE: PLEASE SEE MISSING REQUIRED LICENSE |
| INFORMATION ON TITLE BLOCKS FOR EFP SHEETS. PLEASE SEE |
| FS 471.023 WHICH REQUIRES A CERTIFICATE OF |
| AUTHORIZATION NUMBER AND TO BE PLACED ON TITLE BLOCKS. |
| THIS IS FOR SACRAMENTO ENGINEERING. |
| **THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| OTHER TRADES. |
| |
| 5) NOTE: THIS IS THE SAME COMMENT AS PREVIOUS REVIEW AS |
| THE PLANS WERE NOT CHANGED. PLEASE SEE THE A SHEETS |
| STILL INDICATE TWO CODES. THE FA/EFP SHEETS INDICATE |
| CODES NOT UNDER THE FBC. (IBC,IFC ) |
| |
| **PREVIOUS REVIEW NOTE** |
| PLEASE SEE THE PREVIOUS REVIEWS WHICH MENTIONED THE |
| CODES REQUIRED DEPENDING ON WHEN PERMIT APPLICATION IS |
| MADE. PLEASE SEE THE PLANS NOW LIST BOTH CODES FOR 2005 |
| AND 2002 ARE BEING SHOWN ON PLANS FOR DESIGN ETC?? |
| PLEASE MAKE THE CORRECTIONS. |
| PLEASE SEE THE 2005 NFPA-70 AND THE 2004 FBC REVISIONS |
| #6 WILL BE REQUIRED. |
| PLEASE SEE NUMEROUS SECTIONS OF THE FIRE SHEETS WHICH |
| SPECIFY THE 1996 NFPA-72 AND OTHER CODES NOT ADOPTED |
| UNDER THE STATE. PLEASE SEE ALL OF THE NEW CODES |
| ADOPTED IN THE REFERENCE TABLES AND CORRECT PLANS. |
| |
| 6) NOTE:PLEASE SEE THE NOTES WITH RESPECT TO FBC |
| CHAPTER 13 REMAIN IN AFFECT. |
| PLEASE SEE THE ENERGY CALCULATIONS ARE NOT PER |
| 13-415.1.AB.1.1. PLEASE SEE THE PROGRAM OF FLA-COM |
| VERSION 3.0 IS THE LATEST EDITION ADOPTED BY THE STATE |
| AND CHAPTER 13. |
| WHEN THESE ARE DONE, THE ENERGY CALCULATIONS MUST ALSO |
| CONTAIN THE INPUT DATA REPORT TO COINCIDE WITH THE |
| PLANS FOR REVIEW. |
| PLEASE SEE THESE WILL BE REQUIRED TO BE SIGNED, DATED |
| AND SEALED AS PREVIOUSLY NOTED. THE FLA-COM SHEETS HAVE |
| SPACE FOR THIS. |
| PLEASE SEE NOT ALL SEPARATE SPACES WHICH CONTAIN FLOOR |
| TO CEILING HEIGHT PARTITIONS CONTAIN CONTROLS AS |
| REQUIRED PER 13-415.1.ABC.1.1, .1.2. |
| PLEASE SEE SYMBOL LEGEND DOES NOT STATE TIMES OF |
| DEVICES. |
| PLEASE COORDINATE ALL DOCUMENTS. |
| RESPONSE FROM DESIGNER ONLY RESPONDED TO ONE OF THE |
| COMMENTS MADE IN THIS NOTE FROM PREVIOUS REVIEW. |
| |
| ** PREVIOUS REVIEW NOTES** |
| PLEASE SEE THAT THE ENERGY CALCULATIONS SUBMITTED ARE |
| STILL NOT SIGNED, DATED AND SEALED BY THE DESIGNER OF |
| RECORD NOR ARE THEY UNDER THE CORRECT CODE. THEY ARE |
| DONE AND SUBMITTED UNDER THE 2001 IEC WHICH IS NOT IN |
| EFFECT IN THE STATE OF FLORIDA. PLEASE SEE BOTH |
| PREVIOUS REVIEWS WHICH MENTION TO SEE 13-415.1.AB.1.1, |
| 13-415.2 AND 13-103.1.1.1. |
| REVIEW FOR COMPLIANCE OF CHAPTER 13 CAN NOT BE DONE AT |
| THIS TIME. PLEASE ALSO SEE THAT UNDER THE 2006 |
| REVISIONS TO THE 2004 FBC CONTAINS CHANGES TO CHAPTER |
| 13. |
| PLEASE SEE PREVIOUS NOTE FOR DEVICES ON RESTROOMS, |
| WHICH IS NOT CLEAR WHETHER OR NOT THEY CONTAIN |
| COVERAGE. PLEASE SPECIFY THE TYPE OF DEVICES. PLEASE |
| SEE NOT INFORMATION IS SPECIFIED FOR MAXIMUM TIMES ON |
| OVER RIDE OF THESE DEVICES AND OTHER SYSTEMS, TIME |
| SCHEDULING ETC. |
| PLEASE SUBMIT COMPLETED PLANS FOR COMPLIANCE WITH |
| CHAPTER 13. |
| |
| PLEASE SEE 2004 FBC W/ 2006 REVISIONS CHAPTER 13. |
| PLEASE SEE 13-413.1ABC.1, PROVIDE WORST CASE FOR |
| FEEDERS AND BRANCH CIRCUITS. |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3. |
| PLEASE PROVIDE LIGHTING CONTROL/ ENERGY MANG SYSTEM |
| DETAILS. |
| PLEASE SEE 13-415.1.AB.1, 13-415.2.ABC.1 FOR TABLES |
| 415.2.C.1 AND 415.2.B.1. |
| PLEASE ALSO BE SURE ALL ENERGY CALCULATIONS ARE SIGNED, |
| DATED AND SEALED BY THE DESIGNER(S) OF RECORD. |
| |
| 7) NOTE:PLEASE SEE THIS WAS THE NOTE FROM PREVIOUS |
| REVIEW. THIS REMAINS, AS ONLY SOME SHEETS WERE REVISED |
| TO CHANGE DOOR SWING. PLEASE SEE SHEETS WHICH WERE NOT |
| REVISED STILL INDICATE INWARD SWING ON DOOR. |
| ** PREVIOUS REVIEW NOTE ** |
| THIS IS TAKEN FROM PREVIOUS REVIEW AS NO CHANGES TO |
| ROOM LAYOUT OR DOOR HAS BEEN MADE. PLEASE SEE THE MAIN |
| ELECTRICAL ROOM SHALL CONTAIN A CLEAR AND UNOBSTRUCTED |
| PATH WHICH IT DOES NOT. THERE IS A WALL CLEARLY SHOWN |
| WHICH WOULD IMPEDE THE EGRESS OUT OF THE ROOM IN AN |
| EMERGENCY. IN THE CASE OF FIRE OR BLINDNESS, AN |
| ELECTRICIAN OR OTHER PERSON COULD BECOME TRAPPED AND |
| THIS SCENARIO CREATES A LIFE SAFETY ISSUE WHICH IS NOT |
| ACCEPTABLE TO THIS AHJ. PLEASE ALSO SEE THAT THE DOOR |
| WILL BE REQUIRED TO OPEN OUTWARD AND WILL BE REQUIRED |
| TO CONTAIN PANIC HARDWARE. |
| 110.26, 90.4 |
| |
| 8) NOTE: PLEASE SHOW ALL STROBES/HORN DEVICES NEW OR |
| EXISTING MEETING THE 2004 FBC CHAPTER 11. 11-4.28.1, |
| .2, AND .3(4). |
| PLEASE SEE NOTE ABOVE WITH RESPECT TO NUMEROUS CODES |
| AND SECTIONS BEING REFERENCE ON THE FIRE PROTECTION |
| SHEETS WHICH ARE FROM TWO CODE CYCLES AGO. |
| PLEASE ALSO KNOW THAT WE ARE ALSO CURRENTLY UNDER THE |
| 2002 NFPA-72 |
| |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |