2007-06-27 18:57:55 | ADD: 6901 OKEECHOBEE BLVD. |
| CONT:PLAN REVIEW |
| KATIE GRINDEL (913)236-3437 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 4TH REVIEW |
| ACTION: DENIED |
| |
| NOTE IN FOR PLAN REVIEW ONLY, WILL NEED TO CONFORM TO |
| THE FBC 2004 WITH 2006 REVISIONS. |
| |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT BEFORE A |
| PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| NOT ACTUALLY COMMENCED |
| WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. |
| |
| 3-8) COMPLIED. |
| |
| 10A) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A-E) COMPLIED |
| F)ROOFING ASSEMBLIES THERE ARE CURRENTLY SUBMITTED ARE |
| FOUR (4) DIFFERENT ROOFING PRODUCT APPROVALS SUBMITTED |
| TO THE CITY: |
| JOHN MANVILLE FL 1037-R1HASTHE BRR |
| ARCHITECTURAL REVIEW STAMP |
| JOHN MANVILLE FL644-R2HASTHE BRR |
| ARCHITECTURAL REVIEW STAMP |
| JOHN MANVILLE FL2948-R1NOT REVIEWED |
| GAF FL618-R1HASTHE BRR |
| ARCHITECTURAL REVIEW STAMP |
| |
| |
| GAF BUILT UP ROOF: NO SUBSYSTEM HAS BEEN HIGHLIGHTED IN |
| THE REPORT SUBMITTED . UNDER THE FLORIDA COVERSHEET THE |
| MIAMI-DADE REPORT IS HIGHLIGHTED (03-0430.11) BUT THE |
| INDIVIDUAL SUBSYSTEMS LISTED WITHIN THE REPORT ARE NOT |
| HIGHLIGHTED INDICATING WHICH SUBSYSTEM AND ASSOCIATED |
| PRESSURES WILL BE USED. PAGES 7-19, PLEASE HIGHLIGHT |
| AND SEE MAXIMUM DESIGN PRESSURES LISTED. IF GENERAL |
| LIMITATION # 7 |
| IS INDICATED AND ZONES 2 & 3 REQUIRE ENHANCED FASTENING |
| PLEASE PROVIDE THE CALCULATIONS FOR RAS 117. IF |
| LIMITATION # ( IS INDICATED NO ENHANCED FASTENING CAN |
| TAKE PLACE. |
| G) JOHN MANSVILLEBUILT UP ROOF: NO SUBSYSTEM HAS BEEN |
| HIGHLIGHTED IN THE REPORT SUBMITTED . UNDER THE FLORIDA |
| COVERSHEET THE MIAMI-DADE REPORT IS HIGHLIGHTED |
| (03-0430.11) BUT THE INDIVIDUAL SUBSYSTEMS LISTED |
| WITHIN THE REPORT ARE NOT HIGHLIGHTED INDICATING WHICH |
| SUBSYSTEM AND ASSOCIATED PRESSURES WILL BE USED. PAGES |
| 7-19, PLEASE HIGHLIGHT AND SEE MAXIMUM DESIGN PRESSURES |
| LISTED. IF GENERAL LIMITATION # 7IS INDICATED AND |
| ZONES 2 & 3 REQUIRE ENHANCED FASTENING PLEASE PROVIDE |
| THE CALCULATIONS FOR RAS 117. IF LIMITATION # ( IS |
| INDICATED NO ENHANCED FASTENING CAN TAKE PLACE. |
| H) ROOF HATCHES: SEE PALM BEACH COUNTY BUILDING CODE |
| ADVISORY BOARD TECHNICAL ADVISORY |
| I) OVERHEAD GARAGE DOOR: NO REPORTS WAS SUBMITTED, ONLY |
| THE FLORIDA COVER SHEET, THERE ARE (3) SERIES 591 TO |
| PICK FROM WHICH ARE YOU GOING TO USE? |
| |
| |
| JOHN MANSVILLE REPORT FL644-R2 MIAMI-DADE NOA SHEET 11 |
| ISSTARRED, THE MAXIMUM DESIGN PRESSURE IS -52.5 |
| LIMITATION NUMBER (7) REQUIRES AN ENGINEER , ARCHITECT |
| OR REGISTERED ROOFING CONSULTANT TO RUN THE RAS 117 |
| CALCULATION FOR ROOF ZONES 2 & 3.IF THIS PRODUCT IS |
| PICKED PLEASE REMOVE ALL OTHER ROOFING APPROVALS FROM |
| THE PACKAGE. |
| |
| THERE ARE TWO OTHER JOHN MANVILLE PRODUCT APPROVALS |
| WITH NOTHING HIGHLIGHTED. |
| |
| |
| 10B) OUTSWING STEEL DOOR BY REPUBLIC BUILDERS HAS NOT |
| BEEN APPROVED BY THE DESIGNER OF RECORD, PLEASE REVIEW |
| AND STAMP WITH SHOP DRAWING STAMP. |
| |
| 11) COMPLIED. |
| |
| 12) ROOF HAATCHES: IF THERE ARE NO STATE OR MIAMI-DADE |
| REPORTS AVAILABLE THEN A LOCAL PRODUCT APPROVAL REPORT |
| WITH THIRD PARTY QUALITY ASSURANCE PROGRAM WILL BE AN |
| OPTION. THE ROOF HATCH SUBMITTAL FROM BABCOCK-DAVIS |
| DOES NOT MEET THE REQUIREMENTS FOR A LOCAL PRODUCT |
| APPROVAL THERE HAS TO BE AN INDEPENDENT TEST DONE BY A |
| LAB LISTED ON THE STATE WEB SITE PLUS THETHIRD PARTY |
| QUALITY ASSURANCEENTITY THAT ARE ALSO LISTED ON THE |
| STATE WEBSITE |
| ADDRESS IS FLORIDABUILDING.ORG. |
| NOTE; BILCO HATCH IS CURRENTLY UNDERGOING TESTING AND |
| IS SUPPOSE TO HAVE REPORTS BY THE END OF SUMMER. |
| |
| 13) COVERSHEET BUILDING TYPE IS AGAIN WRONG, THIS IS |
| NOT A TYPE 5B BUILDING IS A 4HR FIRE WALL A TYPE IIIB |
| MERCANTILE AND OR BUSINESS OCCUPANCY |
| HAS UNLIMITED AREA WHEN FULLY SPRINKLED AND 60 FT |
| CLEARENCE AROUND THE BUILDING. SEE SECTION 507.2 |
| |
| 14) COVERSHEET MAXIMUM FLOOR AREA ALLOWABLE REFRENENCES |
| THE 2003 IBC PLEASE CORRECT. |
| |
| 15) COVERSHEET: TOTAL SQ FT BUILDING SIZELISTED IS |
| 50,790 THIS IS THIS TENANT SPACE, NOT BUILDING SQ FT |
| UNLESS THERE ARE 4 HR WALLS ON EACH SIDE OF THE |
| BUILDING! PLANS DO NOT INDICATE THIS! |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
2007-04-03 08:20:00 | "PLAN REVIEW" I |
| PERMIT: 06070683 |
| ADD: 6901 OKEECHOBEE BLVD. |
| CONT:PLAN REVIEW |
| KATIE GRINDEL (913)236-3437 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 3RDREVIEW |
| ACTION: DENIED |
| |
| NOTE IN FOR PLAN REVIEW ONLY, WILL NEED TO CONFORM TO |
| THE FBC 2004 WITH 2006 REVISIONS. |
| |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT BEFORE A |
| PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| NOT ACTUALLY COMMENCED |
| WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. |
| |
| 3-8) COMPLIED. |
| |
| 10) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A-E) COMPLIED |
| F) GAF BUILT UP ROOF: NO SUBSYSTEM HAS BEEN HIGHLIGHTED |
| IN THE REPORT SUBMITTED . UNDER THE FLORIDA COVERSHEET |
| THE MIAMI-DADE REPORT IS HIGHLIGHTED (03-0430.11) BUT |
| THE INDIVIDUAL SUBSYSTEMS LISTED WITHIN THE REPORT ARE |
| NOT HIGHLIGHTED INDICATING WHICH SUBSYSTEM AND |
| ASSOCIATED PRESSURES WILL BE USED. PAGES 7-19, PLEASE |
| HIGHLIGHT AND SEE MAXIMUM DESIGN PRESSURES LISTED. IF |
| GENERAL LIMITATION # 7 |
| IS INDICATED AND ZONES 2 & 3 REQUIRE ENHANCED FASTENING |
| PLEASE PROVIDE THE CALCULATIONS FOR RAS 117. IF |
| LIMITATION # ( IS INDICATED NO ENHANCED FASTENING CAN |
| TAKE PLACE. |
| G) JOHN MANSVILLEBUILT UP ROOF: NO SUBSYSTEM HAS BEEN |
| HIGHLIGHTED IN THE REPORT SUBMITTED . UNDER THE FLORIDA |
| COVERSHEET THE MIAMI-DADE REPORT IS HIGHLIGHTED |
| (03-0430.11) BUT THE INDIVIDUAL SUBSYSTEMS LISTED |
| WITHIN THE REPORT ARE NOT HIGHLIGHTED INDICATING WHICH |
| SUBSYSTEM AND ASSOCIATED PRESSURES WILL BE USED. PAGES |
| 7-19, PLEASE HIGHLIGHT AND SEE MAXIMUM DESIGN PRESSURES |
| LISTED. IF GENERAL LIMITATION # 7IS INDICATED AND |
| ZONES 2 & 3 REQUIRE ENHANCED FASTENING PLEASE PROVIDE |
| THE CALCULATIONS FOR RAS 117. IF LIMITATION # ( IS |
| INDICATED NO ENHANCED FASTENING CAN TAKE PLACE. |
| H) ROOF HATCHES: SEE PALM BEACH COUNTY BUILDING CODE |
| ADVISORY BOARD TECHNICAL ADVISORY |
| I) OVERHEAD GARAGE DOOR: NO REPORTS WAS SUBMITTED, ONLY |
| THE FLORIDA COVER SHEET, THERE ARE (3) SERIES 591 TO |
| PICK FROM WHICH ARE YOU GOING TO USE? |
| |
| 11) COMPLIED. |
| |
| 12) ROOF HAATCHES: IF THERE ARE NO STATE OR MIAMI-DADE |
| REPORTS AVAILABLE THEN A LOCAL PRODUCT APPROVAL REPORT |
| WITH THIRD PARTY QUALITY ASSURANCE PROGRAM WILL BE AN |
| OPTION. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |