Plan Review Notes
Plan Review Notes For Permit 06070683
Permit Number 06070683
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2007-03-22 15:47:07******UNSAT******
  
 *PLEASE ADDRESS THE FOLLOWING COMMENTS TAKEN FROM THE
 PREVIOUS FIRE PLAN REVIEW:
  
  
  
 07.)FIRE ALARM SYSTEM SHALL BE FULLY ADDRESSABLE AND
 SHALL BE UL CERTIFIED FOR CENTRAL STATION SERVICE.
 ADD THIS COMMENT TO SHEET EFP2
  
 08.)DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL
 FIRE ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
 MAKE THE NECESSARY CORRECTIONS ON SHEET EFP2, UNDER
 AHJ/COMPLIANCE NOTE #8 AND ALSO IN THE SEQUENCE OF
 OPERATIONS DETAIL,TO REFLECT THIS OPERATION.
  
 *NEW CMMENT:
  
  
 1.IN REGARDS TO NFPA 72, NATIONAL FIRE ALARM CODE,
 THE 2002 EDITION (NOT 1996) SHOULD BE REFERENCED.MAKE
 THE NECESSARY CORRECTIONS ON SHEET EFP2.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722