Plan Review Notes For Permit 06070683 |
Permit Number |
06070683 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-03-22 15:47:07 | ******UNSAT****** | | | | *PLEASE ADDRESS THE FOLLOWING COMMENTS TAKEN FROM THE | | PREVIOUS FIRE PLAN REVIEW: | | | | | | | | 07.)FIRE ALARM SYSTEM SHALL BE FULLY ADDRESSABLE AND | | SHALL BE UL CERTIFIED FOR CENTRAL STATION SERVICE. | | ADD THIS COMMENT TO SHEET EFP2 | | | | 08.)DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL | | FIRE ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | MAKE THE NECESSARY CORRECTIONS ON SHEET EFP2, UNDER | | AHJ/COMPLIANCE NOTE #8 AND ALSO IN THE SEQUENCE OF | | OPERATIONS DETAIL,TO REFLECT THIS OPERATION. | | | | *NEW CMMENT: | | | | | | 1.IN REGARDS TO NFPA 72, NATIONAL FIRE ALARM CODE, | | THE 2002 EDITION (NOT 1996) SHOULD BE REFERENCED.MAKE | | THE NECESSARY CORRECTIONS ON SHEET EFP2. | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|