2007-02-20 15:17:50 
 ********** UNSAT 3RD REVIEW *************
  
 ********** WAL-MART BUILD -OUT******
  
 ** PLEASE SEE PLANS ARE STILL ONLY SUBMITTED FOR "PLAN
 REVIEW" AND HAVE NOT BEEN SUBMITTED FOR PERMIT.
  
 1 NOTE: PLEASE KNOW THAT IT IS MOST HELPFUL FOR A
 REVIEW IF A RESPONSE LETTER OF SOME TYPE IS SUBMITTED
 BY THE DESIGNER OF RECORD. PLEASE SEE THE RESPONSE
 LETTER CONTAINS TWO RESPONSES WHICH ARE BOTH LISTED AS
 ITEM #1 AND DO NOT INDICATE WHAT THEY ARE BEING
 RESPONDED TO??
  
 2) NOTE:PLEASE SEE THE PREVIOUS REVIEWS WHICH
 MENTIONED THE CODES REQUIRED DEPENDING ON WHEN PERMIT
 APPLICATION IS MADE. PLEASE SEE THE PLANS NOW LIST BOTH
 CODES FOR 2005 AND 2002 ARE BEING SHOWN ON PLANS FOR
 DESIGN ETC?? PLEASE MAKE THE CORRECTIONS.
 PLEASE SEE THE 2005 NFPA-70 AND THE 2004 FBC REVISIONS
 #6 WILL BE REQUIRED.
 PLEASE SEE NUMEROUS SECTIONS OF THE FIRE SHEETS WHICH
 SPECIFY THE 1996 NFPA-72 AND OTHER CODES NOT ADOPTED
 UNDER THE STATE. PLEASE SEE ALL OF THE NEW CODES
 ADOPTED IN THE REFERENCE TABLES AND CORRECT PLANS.
  
 3) NOTE:PLEASE SEE THAT THE ENERGY CALCULATIONS
 SUBMITTED ARE STILL NOT SIGNED, DATED AND SEALED BY THE
 DESIGNER OF RECORD NOR ARE THEY UNDER THE CORRECT CODE.
 THEY ARE DONE AND SUBMITTED UNDER THE 2001 IEC WHICH IS
 NOT IN EFFECT IN THE STATE OF FLORIDA. PLEASE SEE BOTH
 PREVIOUS REVIEWS WHICH MENTION TO SEE 13-415.1.AB.1.1,
 13-415.2 AND 13-103.1.1.1.
 REVIEW FOR COMPLIANCE OF CHAPTER 13 CAN NOT BE DONE AT
 THIS TIME. PLEASE ALSO SEE THAT UNDER THE 2006
 REVISIONS TO THE 2004 FBC CONTAINS CHANGES TO CHAPTER
 13.
 PLEASE SEE PREVIOUS NOTE FOR DEVICES ON RESTROOMS,
 WHICH IS NOT CLEAR WHETHER OR NOT THEY CONTAIN
 COVERAGE. PLEASE SPECIFY THE TYPE OF DEVICES. PLEASE
 SEE NOT INFORMATION IS SPECIFIED FOR MAXIMUM TIMES ON
 OVER RIDE OF THESE DEVICES AND OTHER SYSTEMS, TIME
 SCHEDULING ETC.
 PLEASE SUBMIT COMPLETED PLANS FOR COMPLIANCE WITH
 CHAPTER 13.
  
 PLEASE SEE 2004 FBC W/ 2006 REVISIONS CHAPTER 13.
 PLEASE SEE 13-413.1ABC.1, PROVIDE WORST CASE FOR
 FEEDERS AND BRANCH CIRCUITS.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3.
 PLEASE PROVIDE LIGHTING CONTROL/ ENERGY MANG SYSTEM
 DETAILS.
 PLEASE SEE 13-415.1.AB.1, 13-415.2.ABC.1 FOR TABLES
 415.2.C.1 AND 415.2.B.1.
 PLEASE ALSO BE SURE ALL ENERGY CALCULATIONS ARE SIGNED,
 DATED AND SEALED BY THE DESIGNER(S) OF RECORD.
  
 4) NOTE: THIS IS TAKEN FROM PREVIOUS REVIEW AS NO
 CHANGES TO ROOM LAYOUT OR DOOR HAS BEEN MADE. PLEASE
 SEE THE MAIN ELECTRICAL ROOM SHALL CONTAIN A CLEAR AND
 UNOBSTRUCTED PATH WHICH IT DOES NOT. THERE IS A WALL
 CLEARLY SHOWN WHICH WOULD IMPEDE THE EGRESS OUT OF THE
 ROOM IN AN EMERGENCY. IN THE CASE OF FIRE OR BLINDNESS,
 AN ELECTRICIAN OR OTHER PERSON COULD BECOME TRAPPED AND
 THIS SCENARIO CREATES A LIFE SAFETY ISSUE WHICH IS NOT
 ACCEPTABLE TO THIS AHJ. PLEASE ALSO SEE THAT THE DOOR
 WILL BE REQUIRED TO OPEN OUTWARD AND WILL BE REQUIRED
 TO CONTAIN PANIC HARDWARE.
 110.26, 90.4
  
 5) NOTE: PLEASE SEE THAT THE PANEL LRX WHICH IS STILL
 BEING SHOWN IN A STORAGE ROOM. PLEASE RELOCATE. THIS IS
 A LIFE SAFETY AND PROPERTY SAFETY ISSUE AND WILL NOT BE
 PERMITTED IN THIS ROOM.
 PLEASE SEE 110.26, 408.7, AND 240.24 AS STORAGE OF ANY
 TYPE FOR MIN CLEARANCES, COMBUSTIBLES OF EASILY
 IGNITABLE MATERIALS ETC.
  
 6) NOTE: PLEASE SEE PLANS STILL FOR A KIRK KEY
 INTERLOCK WHICH DOES NOT PROVIDE A *FAIL SAFE*
 OPERATION. THIS OFFICE HAS REVIEWED DOCUMENTATION
 PROVIDED. THIS OFFICE HAS NOT MENTIONED THAT A LISTED
 TRANSFER SWITCH IS REQUIRED HOWEVER WE ARE REQUIRING
 THE DEVICE IS LISTED FOR USE AND THAT IT PROVIDES
 COMPLETE FAIL SAFE OPERATION.
 DEVICES AS SUBMITTED DO NOT PROVIDE THIS REQUIREMENT.
 PLEASE SEE 110.3, 90.7, 702.6 ETC.
 PLEASE SUBMIT ACTUAL SPEC/MANUFACTURES CUT SHEETS.
  
 7) NOTE: PLEASE SHOW ALL STROBES/HORN DEVICES NEW OR
 EXISTING MEETING THE 2004 FBC CHAPTER 11. 11-4.28.1,
 .2, AND .3(4).
 PLEASE SEE NOTE ABOVE WITH RESPECT TO NUMEROUS CODES
 AND SECTIONS BEING REFERENCE ON THE FIRE PROTECTION
 SHEETS WHICH ARE FROM TWO CODE CYCLES AGO.
 PLEASE ALSO KNOW THAT WE ARE ALSO CURRENTLY UNDER THE
 2002 NFPA-72
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-02-19 10:37:322007-02-19 10:37:32
 REVIEW TO CONTINUE ON 2/20 NOTES TO FOLLOW , PLANS WILL
 BE PLACED INTO A "F" STATUS.