2006-12-12 14:04:42 | |
| "PLAN REVIEW" I |
| PERMIT: 06070683 |
| ADD: 6901 OKEECHOBEE BLVD. |
| CONT:PLAN REVIEW |
| KATIE GRINDEL (913)236-3437 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 3RDREVIEW |
| ACTION: DENIED |
| |
| NOTE IN FOR PLAN REVIEW ONLY, WILL NEED TO CONFORM TO |
| THE FBC 2004 WITH 2006 REVISIONS. |
| |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT BEFORE A |
| PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| NOT ACTUALLY COMMENCED |
| WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. |
| |
| 3) COMPLIED. |
| |
| 4A) THE THREE NUMBERS SUPPLIED ON THE PLAN FOR THE |
| CERTIFICATE OF AUTHORIZATION NONE ARE THE COA FOR |
| FLORIDA. |
| PLEASE PROVIDE THIS NUMBER ON ALL SHEETS REQUIRED, |
| AA26001022 |
| |
| 4B) THE OTHER ISSUE WITH THE DBA NAME IS BOICE RAIDL |
| RAIDL ARCHITECTECTS INC. NOT THE BRR. |
| |
| 5) THIS REQUEST IS FOR THE WHOLE BUILDING, NOT TENANT |
| SPACE, UNLESS THE DEMISSING WALLS ARE 4 HR FIRE WALLLS |
| BREAKING THIS TENANT SPACE INTO A SEPERATE BUILDING WE |
| NEED THE AREA FOR THE COMPLETE BUILDINGPLEASE SHOW THE |
| AREA INCREASES ON THE PLANS THE NOTE SUBMITTALS ARE |
| THROWN OUT ONCE THE PERMIT IS ISSUED. TABLE 503. 5) |
| SHEET C-1 BUILDING CODE SUMMARY, TYPE |
| OF CONSTRUCTION, PLANS INDICATE A VB, |
| FOR MERCANTILE TABLE 503 INDICATES AN |
| ALLOWABLE 9,000 SQ FT. PLEASE PROVIDE |
| WHAT INCREASES WERE TAKEN TO ACHIEVE THE |
| 49,960 SQ FT OF ACTUAL BUILDING?PROVIDE |
| CALCULATIONS.NOW THIS IS GOING TO BE FOR |
| THE BUILDING NOT TENANT SPACE!!!!! |
| |
| 6) COMPLIED. |
| |
| 7) COMPLIED. |
| |
| 8) MOST OF THE PRODUCT APPROVALS THAT HAVE FLORIDA |
| REPORTS HAVE BEEN PRINTED. |
| THERE IS A COMMENT ON EACH REPORT THAT STILL REQUIRES |
| FLORIDA APPROVAL COVER SHEETS.PRODUCT APPROVALS |
| SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 9) 2ND REQUEST,THE DESIGN PROFESSIONALS STILL HAVE |
| NOT REVIEWED AND APPROVED ANY REPORTS, |
| )W P B ADMINISTRTIVE CODE 106.3.3* |
| PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| |
| 10) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) OVERHEAD DOORS - COMPLIED. |
| B) STANLEY ACCESS- COMPLIED. |
| C) REPUBLIC BUILDERS PRODUCTS- COMPLIED. |
| D) CURRIES EXTERIOR DOORS- COMPLIED |
| E)CECO DOORS NEED THE MANUFACTURERS RECOMENDED |
| ERECTIION INSTRUCTION, INSPECTOR TO VERIFY THE PSF ON |
| SITE. |
| F) GAF BUILT UP ROOF NO SUBSYSTEM HAS BEEN HIGHLIGHTED |
| AS TO WHICH WILL BE USED, PLEASE NOTE LIMITATIONS.G) |
| JOHNS MANVILEE MODIFIED SAME COMMENT AS ABOVE. H) ROOF |
| HATCHES RULE 9B-72 THE REVISIONS EFFECTIVE 1-01-06 |
| REQUIRE PRE-ENGINEERED |
| ROOF ACCESS HATCHES TO HAVE APPROVALS. ACOPY OF THIS |
| STATEMENT IS ATTACHED. |
| I) PRE-ENGINEERED A/C STANDS- NOT CURBS CURBS ARE SHOWN |
| DETIAL# 3 S-5. |
| |
| 12) DEALS WITH THE REQUIRIMENT FOR PRODUCT APPROVALS |
| SEE 10H AND ATTACHMENT. BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |