Date |
Text |
2007-01-13 07:23:58 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. ALL SHEETS DESIGNED BY THE REGISTERED ARCHITECT. THE |
| ORIGINAL SIGNATURE IS |
| REQUIRED ON THE SEAL, AND THE BUSINESS |
| LICENSE NUMBER, (CERTIFICATE OF |
| AUTHORIZATION), IS REQUIRED IN THE TITLE |
| BLOCK OF EACH SHEET. 61G1-16.004(1)(5) |
| AND FS 481.219 481.2055. |
| ****RESPONSE NOTED, BUT THE CERTIFICATE OF |
| AUTHORIZATION IS NOT INDICATED IN THE TITLE BLOCK OF |
| THE ARCHITECT. (SEE ATTACHED SHEET FROM THE DBPR |
| WEBSITE INDICATE PROPER BUSINESS NUMBER). |
| |
| 2. OK |
| 3. OK |
| 4. OK |
| 5. OK |
| 6. OK |
| |
| 7. A5.3 FAMILY TOILET ROOM, (129), |
| WOMENS TOILET ROOM, (130), MEN'S TOILET |
| FOOM, (127). SHALL BE ACCESSIBLE. SUBMIT |
| THE FOLLOWING: |
| FOR W/C'S... |
| A. OK |
| B. OK |
| C. OK |
| D. OK |
| FOR STALLS.... |
| A. 11-4.17.3 EXCEPTION 2 THE ACCESSIBLE |
| W/C SHALL BE LOCATED IN THE CORNER, |
| DIAGONAL TO THE DOOR. (SEE MENS TOILET |
| ROOM). |
| ****NOT ADDRESSED |
| FOR URINALS... |
| A. OK |
| B. 11-4.18.4 FLUSH CONTROLS |
| ****NOT ADDRESSED |
| FOR LAVS.... |
| A. OK |
| B. OK |
| C. 11-4.19.5 FAUCETS |
| ****NOT ADDRESSED |
| D. OK |
| |
| 8. OK |
| 9. OK |
| |
| 10. ALL PME & REFRIG. SHEETS. ENGINEERS |
| SHALL LEGIBLY INDICATE THEIR NAME, AND |
| LICENSE NUMBER, AS WELL AS, THE NAME, |
| ADDRESS AND CERTIFICATE OF AUTHORIZATION |
| NUMBER OF THE ENGINEERING BUSINESS ON |
| EACH SHEET. 61G15-23.002(2) & FS 471.025. |
| ****RESPONSE NOTED, BUT THE LICENSE NUMBER IS NOT |
| INDICATED IN THE TITLE BLOCK. |
| |
| 11. SHT P1 GREASE INTERCEPTORS SHALL BE |
| SIZED BY THE UTILITY DEPT. ENVIRONMENTAL COMPLIANCE |
| MGR. PLEASE CONTACT LYNN |
| MASSON, (561) 822-2271, FAX (561) |
| 822-2279, OR E-MAIL [email protected] FOR |
| A DETERMINATION ON INTERCEPTOR SIZE. |
| WASTE ORDINANCE #3434. |
| ****RESPONSE NOTED, WAITING FOR A DETERMINATION FROM |
| MR. WILLIAMS. NO MORE ACTION REQUIRED BY THE |
| CONTRACTOR. |
| |
| 12. OK |
| 13. OK |
| 14. OK |
| |
| 15. SHT P-3 WATER HAMMER ARRESTORS ARE |
| REQUIRED AT ALL QUICK CLOSING VALVES, |
| SUCH AS DISH WASHERS, ICE MAKERS, ETC. |
| PLEASE SHOW ONE AT THE ICE MAKER. ALL |
| WATER HAMMER ARRESTORS SHALL BE LOCATED |
| NEAR THE FIXTURES, IN AN "EFFECTIVE |
| RANGE" NOT IN THE CEILING AS SHOWN AT |
| THE LAVS IN MENS AND WOMENS TOILET ROOM. |
| SECTION 604.9 AND PDI-WH 201. |
| ****RESPONSE NOTED, BUT THE WATER HAMMER ARRESTOR IS |
| REQUIRED AT FIXTURE MG07 ICE MAKER. |
| |
| 16. OK |
| 17. OK |
| 18. OK |
| 19. OK |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |