2006-12-13 15:31:02********2ND PLAN CHECK ONLY*******
  
  
 1.PLEASE PROVIDE ENERGY CALCULATIONS IN ACCORDANCE
 WITH 2004 FBC CHAPTER 13 SECTION 13-101.1.3.
  
 2.PLEASE PROVIDE ANCHORING DETAILS FOR THE CURBS TO
 THE ROOF DECK.PLEASE NOTE CURBS SHALL BE A MINIMUM OF
 8"ABOVE THE ROOF SURFACE PER 2004 FBC 1509.7.
  
 3.EQUIPMENT STANDS LOCATED ON THE ROOF IN WHICH THE
 ROOFING MATERIAL IS REQUIRED UNDER THE STAND, THE
 CLEARANCE REQUIRED BETWEEN THE ROOF SURFACE AND THE
 BOTTOM OF THE SUPPORT RAIL SHALL BE IN ACCORDANCE WITH
 2004 FBC TABLE 1509.7.PLEASE NOTE, PRODUCT APPROVALS
 REQUIRED FOR EQUIPMENT STANDS LOCATED ON THE ROOF.
  
 4.PLAN SHEET M2 OUTSIDE AIR IS INDICATED ON THE
 ROOFTOP UNIT SCHEDULE.PLEASE INDICATE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2004 FMC TABLE 403.3.
  
 5.PLAN SHEET M2 ROOFTOP UNIT SCHEDULE DOES NOT
 INDICATE DUCT SMOKE DETECTOR ON UNITS 1,2, 9, 11 & 12.
 PER 2004 FMC 606.2.1 SMOKE DETECTORS SHALL BE INSTALLED
 INSUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY GREATER
 THAN 2,000 CFM.WHERE MULTIPLE AIR HANDLING SYSTEMS
 WHERE THE AGGREGATE AIR IS GREATER THAN 2,000 CFM, DUCT
 SMOKE DETECTORS WILL BE REQUIRED IN ALL UNITS
 REGARDLESS OF THE THE CAPACITY, 2004 FMC 606.2.2.
  
 PLEASE NOTE, ADDITIONAL PERMITS & PLANS REQUIRED FOR
 THE HOOD, GREASE DUCT & FIRE SUPPRESSION.
  