Plan Review Notes
Plan Review Notes For Permit 06070683
Permit Number 06070683
Review Stop E
Sequence Number 2
Notes
Date Text
2006-12-07 19:12:27********** UNSAT 2ND REVIEW *************
  
 ********** WAL-MART NEW /REMODEL******
  
 ** PLEASE SEE PLANS WERE ONLY SUBMITTED FOR "PLAN
 REVIEW" AND HAVE NOT BEEN SUBMITTED FOR PERMIT. PLEASE
 KNOW THAT AT THIS TIME AS OF DECEMBER 8TH, 2006 THE
 STATE OF FLORIDA ADOPTS NEW CODES AND THESE WILL CHANGE
 AND AFFECT DESIGNS SUBMITTED ON PLANS. PLEASE KNOW THAT
 AS THE PLANS HAVE NOT BEEN SUBMITTED FOR PERMIT
 APPLICATION BEFORE THE END OF TODAY'S DATE, ALL PLANS
 WILL BE REQUIRED TO BE REDESIGNED UNDER THE NEW
 CODE(S).
  
 ** PLEASE SEE SOME COMMENTS BELOW WHICH STILL NEED TO
 BE ADDRESSED. PLEASE SEE SOME OF THESE ARE NOTED WITH A
 "NO" OR "OK". THOSE OF WHICH MAY CONTAIN AN "OK/NO"
 MEANS PART OF THE COMMENT MAY HAVE BEEN ADDRESSED.
  
 ** PLEASE SEE THERE ARE ALSO SOME NEW NOTES.
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE:NO/OK. PLEASE SEE MISSING INFORMATION IS
 STILL REQUIRED FOR THE ARCHITECTURAL FIRM. PLEASE SEE
 THE NUMBER WHICH WAS ADDED TO THE TITLE BLOCKS IS THAT
 OF THE STATE OF FLORIDA'S CORPORATION NUMBER WHICH IS
 NOT THE CERTIFICATE OF AUTHORIZATION NUMBER. PLEASE SEE
 THE NUMBER NEEDED FOR DOING BUSINESS AS AN
 ARCHITECTURAL FIRM IS ISSIED FROM THE DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION.
 THIS IS REQUIRED FOR ALL "A" SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADES.
 THE MEP SHEETS SEEM TO HAVE BEEN ADJUSTED TO INCLUDE
 ONLY THE PE'S AS INDIVIDUALS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED INFORMATION ON TITLE
 BLOCKS FOR ARCHITECTURAL AND ENGINEERING FIRMS. PLEASE
 SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 AND FLORIDA
 STATUES 481.219 FOR THE ARCHITECTURAL FIRM AND PLEASE
 SEE FAC61G15-23.002 AND FS 471.023 FOR THE ENGINEERING
 FIRM.
 PLEASE SEE MISSING PRINTED NAME AND LICENSE NUMBER'S
 FOR INDIVIDUAL DESIGNERS OF RECORD.
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER REQUIRED FOR BOTH FIRMS REQUIRED
 ON TITLE BLOCKS ALSO.
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 4) NOTE:NO, PLEASE SEE THE CODES WERE ADDED AS
 REQUESTED, HOWEVER SINCE A PERMIT HAS NOT BEEN APPLIED
 FOR THE FOLLOWING CODES WILL BE THE NEW RELEVANT CODES
 IN EFFECT TO THE NEW DESIGN. PLEASE SEE THE 2005
 NFPA-70 AND THE 2004 FBC REVISIONS #6 WILL BE
 REQUIRED.
 THE OTHER CODES AS NOTED BELOW WILL REMAIN.
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE PLANS REFLECT THE FOLLOWING CODES AT A
 MINIMUM.
 PLEASE SEE PLANS MENTIONS THE 2004
 FLORIDA ELECTRICAL CODE, HOWEVER CHAPTER
 27 OF THE 2004 FBC ADOPTED THE 2002
 NFPA-70 (NEC).
 PLEASE ALSO LIST THE FOLLOWING.
 NFPA-72 2002, NFPA-101 2003.
  
 5) NOTE:NO, PLEASE SEE AS THE CODE HAS CHANGED THERE
 ARE NOW NEW REQUIREMENTS IN THE SAME SECTIONS AS NOTED
 BELOW. PLEASE SEE HOWEVER THAT THE COMPLETED
 INFORMATION FROM THE PREVIOUS REVIEW WAS NOT ADDRESSED
 AS NEEDED ON PLANS. PLEASE SEE ENERGY CALCULATIONS
 SUBMITTED ARE NOT COMPLETE AS NEEDED. THESE ARE ALSO
 REQUIRED TO BE SIGNED, DATED AND SEALED BY THE DESIGNER
 OF RECORD. PLEASE SEE NO LIGHTING POWER DENSITIES WERE
 SUBMITTED. PLEASE SEE BATH ROOMS WHICH ARE NOT A SINGLE
 STALL, WILL REQUIRE A DIFFERENT TYPE OF OCCUPANCY
 SENSOR TYPE DEVICE. THESE SHALL BE THE TYPE WHICH WILL
 ACTIVATE UNDER OTHER CONDITIONS OTHER THAN MOTION.
 PLEASE SEE AS NO TIMES ON OVER RIDES COULD NOT BE
 LOCATED THERE ARE ITEMS WHICH CAN NOT BE REVIEWED FOR
 COMPLIANCE AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 2004 FBC CHAPTER 13.
 PLEASE SEE 13-413.1ABC.1, PROVIDE WORST CASE FOR
 FEEDERS AND BRANCH CIRCUITS.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3.
 PLEASE PROVIDE LIGHTING CONTROL/ ENERGY MANG SYSTEM
 DETAILS.
 PLEASE SEE 13-415.1.AB.1, 13-415.2.ABC.1 FOR TABLES
 415.2.C.1 AND 415.2.B.1.
 PLEASE ALSO BE SURE ALL ENERGY CALCULATIONS ARE SIGNED,
 DATED AND SEALED BY THE DESIGNER(S) OF RECORD.
  
 6) NOTE: OK.
  
 7) NOTE:NO, PLEASE SEE THE MAIN ELECTRICAL ROOM SHALL
 CONTAIN A CLEAR AND UNOBSTRUCTED PATH WHICH IT DOES
 NOT. THERE IS A WALL CLEARLY SHOWN WHICH WOULD IMPEDE
 THE EGRESS OUT OF THE ROOM IN AN EMERGENCY. IN THE CASE
 OF FIRE OR BLINDNESS, AN ELECTRICIAN OR OTHER PERSON
 COULD BECOME TRAPPED AND THIS SCENARIO CREATES A LIFE
 SAFETY ISSUE WHICH IS NOT ACCEPTABLE TO THIS AHJ.
 PLEASE ALSO SEE THAT THE DOOR WILL BE REQUIRED TO OPEN
 OUTWARD AND WILL BE REQUIRED TO CONTAIN PANIC
 HARDWARE.
 110.26, 90.4
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MINIMUM DOOR/ EGRESS REQUIREMENTS SHALL BE
 REQUIRED FOR MAIN ELECTRICAL ROOM. PLEASE ALSO SEE
 PANIC HARDWARE AND DOORS CHANGES WILL BE REQUIRED FOR
 NEW EQUIPMENT.
  
 8) NOTE:NO, PLEASE SEE RESPONSE LETTER MENTIONS
 STORAGE WILL NOT BE PERMITTED, HOWEVER THIS OFFICE
 INCLUDING THE FIRE MARSHAL?S OFFICE HAS BEEN IN TOO
 NUMEROUS STORAGE ROOMS WHICH MATERIALS ARE PLACED
 IN-FRONT OF EQUIPMENT ETC. THIS IS ALSO A LIFE SAFETY
 HAZARD AND WILL REQUIRE THIS PANEL TO BE RELOCATED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PANEL WHICH IS BEING SHOWN IN STORAGE ROOM
 SHALL BE A DEDICATED ELECTRICAL/EQUIPMENT ROOM OR
 PLEASE RELOCATE PANEL.
 PLEASE SEE 110.26, 408.7, AND 240.24 AS STORAGE OF ANY
 TYPE FOR MIN CLEARANCES, COMBUSTIBLES OF EASILY
 IGNITABLE MATERIALS.
  
 9) NOTE: NO, PLEASE SEE AS OF THE MANUFACTURES
 SPECS/CUT SHEETS SUBMITTED THE EQUIPMENT BEING PROPOSED
 IS NOT ACCEPTABLE TO THIS AHJ AS BEING USED OR
 PROVIDING ANY FAIL SAFE OPERATION OR PROVIDES
 INADVERTENT OPERATION. PLEASE SEE UL LISTING 1081 ETC.
 PLEASE SEE OTHER LISTINGS WHICH WILL REQUIRE THIS
 EQUIPMENT BEING SERVICE ENTRANCE RATED, AND MUST MEET
 SECTIONS GIVEN.
 PLEASE SEE 110.3, 90.7, 702.6 ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT ACTUALSPEC/MANUFACTURES CUT SHEETSFOR
 THE MAIN SW BD AND PROPOSED"KIRK KEY INTERLOCK".
 PLEASE KNOW, THIS OFFICE HAS SEEN SOME SYSTEMS WHICH DO
 NOT MEET THE CODE WITH RESPECT TO TRANSFER EQUIPMENT
 AND LISTED FOR THE INTENDED USE.
 702.6, 110.3
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 ** NEW NOTE **
  
 1) NOTE: PLEASE SHOW ANY STROBES/HORN DEVICES NEW OR
 EXISTING MEETING THE 2004 FBC CHAPTER 11. 11-4.28.1,
 .2, AND .3(4).
 THIS WAS NOT IN PREVIOUS REVIEW AS IT HAS NOW BECOME A
 REQUIRED REVIEW FOR THE ELECTRICAL PLAN REVIEW STAFF.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]