2006-12-07 19:12:27 | ********** UNSAT 2ND REVIEW ************* |
| |
| ********** WAL-MART NEW /REMODEL****** |
| |
| ** PLEASE SEE PLANS WERE ONLY SUBMITTED FOR "PLAN |
| REVIEW" AND HAVE NOT BEEN SUBMITTED FOR PERMIT. PLEASE |
| KNOW THAT AT THIS TIME AS OF DECEMBER 8TH, 2006 THE |
| STATE OF FLORIDA ADOPTS NEW CODES AND THESE WILL CHANGE |
| AND AFFECT DESIGNS SUBMITTED ON PLANS. PLEASE KNOW THAT |
| AS THE PLANS HAVE NOT BEEN SUBMITTED FOR PERMIT |
| APPLICATION BEFORE THE END OF TODAY'S DATE, ALL PLANS |
| WILL BE REQUIRED TO BE REDESIGNED UNDER THE NEW |
| CODE(S). |
| |
| ** PLEASE SEE SOME COMMENTS BELOW WHICH STILL NEED TO |
| BE ADDRESSED. PLEASE SEE SOME OF THESE ARE NOTED WITH A |
| "NO" OR "OK". THOSE OF WHICH MAY CONTAIN AN "OK/NO" |
| MEANS PART OF THE COMMENT MAY HAVE BEEN ADDRESSED. |
| |
| ** PLEASE SEE THERE ARE ALSO SOME NEW NOTES. |
| |
| 1) NOTE: OK. |
| |
| 2) NOTE: OK. |
| |
| 3) NOTE:NO/OK. PLEASE SEE MISSING INFORMATION IS |
| STILL REQUIRED FOR THE ARCHITECTURAL FIRM. PLEASE SEE |
| THE NUMBER WHICH WAS ADDED TO THE TITLE BLOCKS IS THAT |
| OF THE STATE OF FLORIDA'S CORPORATION NUMBER WHICH IS |
| NOT THE CERTIFICATE OF AUTHORIZATION NUMBER. PLEASE SEE |
| THE NUMBER NEEDED FOR DOING BUSINESS AS AN |
| ARCHITECTURAL FIRM IS ISSIED FROM THE DEPARTMENT OF |
| BUSINESS AND PROFESSIONAL REGULATION. |
| THIS IS REQUIRED FOR ALL "A" SHEETS WHETHER OR NOT |
| COMMENT IS MADE BY OTHER TRADES. |
| THE MEP SHEETS SEEM TO HAVE BEEN ADJUSTED TO INCLUDE |
| ONLY THE PE'S AS INDIVIDUALS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE MISSING REQUIRED INFORMATION ON TITLE |
| BLOCKS FOR ARCHITECTURAL AND ENGINEERING FIRMS. PLEASE |
| SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 AND FLORIDA |
| STATUES 481.219 FOR THE ARCHITECTURAL FIRM AND PLEASE |
| SEE FAC61G15-23.002 AND FS 471.023 FOR THE ENGINEERING |
| FIRM. |
| PLEASE SEE MISSING PRINTED NAME AND LICENSE NUMBER'S |
| FOR INDIVIDUAL DESIGNERS OF RECORD. |
| PLEASE SEE MISSING CERTIFICATE OF |
| AUTHORIZATION NUMBER REQUIRED FOR BOTH FIRMS REQUIRED |
| ON TITLE BLOCKS ALSO. |
| ** PLEASE KNOW THIS IS REQUIRED FOR ALL SHEETS AND FOR |
| ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER |
| REVIEWER(S). |
| |
| 4) NOTE:NO, PLEASE SEE THE CODES WERE ADDED AS |
| REQUESTED, HOWEVER SINCE A PERMIT HAS NOT BEEN APPLIED |
| FOR THE FOLLOWING CODES WILL BE THE NEW RELEVANT CODES |
| IN EFFECT TO THE NEW DESIGN. PLEASE SEE THE 2005 |
| NFPA-70 AND THE 2004 FBC REVISIONS #6 WILL BE |
| REQUIRED. |
| THE OTHER CODES AS NOTED BELOW WILL REMAIN. |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE BE SURE PLANS REFLECT THE FOLLOWING CODES AT A |
| MINIMUM. |
| PLEASE SEE PLANS MENTIONS THE 2004 |
| FLORIDA ELECTRICAL CODE, HOWEVER CHAPTER |
| 27 OF THE 2004 FBC ADOPTED THE 2002 |
| NFPA-70 (NEC). |
| PLEASE ALSO LIST THE FOLLOWING. |
| NFPA-72 2002, NFPA-101 2003. |
| |
| 5) NOTE:NO, PLEASE SEE AS THE CODE HAS CHANGED THERE |
| ARE NOW NEW REQUIREMENTS IN THE SAME SECTIONS AS NOTED |
| BELOW. PLEASE SEE HOWEVER THAT THE COMPLETED |
| INFORMATION FROM THE PREVIOUS REVIEW WAS NOT ADDRESSED |
| AS NEEDED ON PLANS. PLEASE SEE ENERGY CALCULATIONS |
| SUBMITTED ARE NOT COMPLETE AS NEEDED. THESE ARE ALSO |
| REQUIRED TO BE SIGNED, DATED AND SEALED BY THE DESIGNER |
| OF RECORD. PLEASE SEE NO LIGHTING POWER DENSITIES WERE |
| SUBMITTED. PLEASE SEE BATH ROOMS WHICH ARE NOT A SINGLE |
| STALL, WILL REQUIRE A DIFFERENT TYPE OF OCCUPANCY |
| SENSOR TYPE DEVICE. THESE SHALL BE THE TYPE WHICH WILL |
| ACTIVATE UNDER OTHER CONDITIONS OTHER THAN MOTION. |
| PLEASE SEE AS NO TIMES ON OVER RIDES COULD NOT BE |
| LOCATED THERE ARE ITEMS WHICH CAN NOT BE REVIEWED FOR |
| COMPLIANCE AT THIS TIME. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE 2004 FBC CHAPTER 13. |
| PLEASE SEE 13-413.1ABC.1, PROVIDE WORST CASE FOR |
| FEEDERS AND BRANCH CIRCUITS. |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3. |
| PLEASE PROVIDE LIGHTING CONTROL/ ENERGY MANG SYSTEM |
| DETAILS. |
| PLEASE SEE 13-415.1.AB.1, 13-415.2.ABC.1 FOR TABLES |
| 415.2.C.1 AND 415.2.B.1. |
| PLEASE ALSO BE SURE ALL ENERGY CALCULATIONS ARE SIGNED, |
| DATED AND SEALED BY THE DESIGNER(S) OF RECORD. |
| |
| 6) NOTE: OK. |
| |
| 7) NOTE:NO, PLEASE SEE THE MAIN ELECTRICAL ROOM SHALL |
| CONTAIN A CLEAR AND UNOBSTRUCTED PATH WHICH IT DOES |
| NOT. THERE IS A WALL CLEARLY SHOWN WHICH WOULD IMPEDE |
| THE EGRESS OUT OF THE ROOM IN AN EMERGENCY. IN THE CASE |
| OF FIRE OR BLINDNESS, AN ELECTRICIAN OR OTHER PERSON |
| COULD BECOME TRAPPED AND THIS SCENARIO CREATES A LIFE |
| SAFETY ISSUE WHICH IS NOT ACCEPTABLE TO THIS AHJ. |
| PLEASE ALSO SEE THAT THE DOOR WILL BE REQUIRED TO OPEN |
| OUTWARD AND WILL BE REQUIRED TO CONTAIN PANIC |
| HARDWARE. |
| 110.26, 90.4 |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE MINIMUM DOOR/ EGRESS REQUIREMENTS SHALL BE |
| REQUIRED FOR MAIN ELECTRICAL ROOM. PLEASE ALSO SEE |
| PANIC HARDWARE AND DOORS CHANGES WILL BE REQUIRED FOR |
| NEW EQUIPMENT. |
| |
| 8) NOTE:NO, PLEASE SEE RESPONSE LETTER MENTIONS |
| STORAGE WILL NOT BE PERMITTED, HOWEVER THIS OFFICE |
| INCLUDING THE FIRE MARSHAL?S OFFICE HAS BEEN IN TOO |
| NUMEROUS STORAGE ROOMS WHICH MATERIALS ARE PLACED |
| IN-FRONT OF EQUIPMENT ETC. THIS IS ALSO A LIFE SAFETY |
| HAZARD AND WILL REQUIRE THIS PANEL TO BE RELOCATED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE PANEL WHICH IS BEING SHOWN IN STORAGE ROOM |
| SHALL BE A DEDICATED ELECTRICAL/EQUIPMENT ROOM OR |
| PLEASE RELOCATE PANEL. |
| PLEASE SEE 110.26, 408.7, AND 240.24 AS STORAGE OF ANY |
| TYPE FOR MIN CLEARANCES, COMBUSTIBLES OF EASILY |
| IGNITABLE MATERIALS. |
| |
| 9) NOTE: NO, PLEASE SEE AS OF THE MANUFACTURES |
| SPECS/CUT SHEETS SUBMITTED THE EQUIPMENT BEING PROPOSED |
| IS NOT ACCEPTABLE TO THIS AHJ AS BEING USED OR |
| PROVIDING ANY FAIL SAFE OPERATION OR PROVIDES |
| INADVERTENT OPERATION. PLEASE SEE UL LISTING 1081 ETC. |
| PLEASE SEE OTHER LISTINGS WHICH WILL REQUIRE THIS |
| EQUIPMENT BEING SERVICE ENTRANCE RATED, AND MUST MEET |
| SECTIONS GIVEN. |
| PLEASE SEE 110.3, 90.7, 702.6 ETC. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SUBMIT ACTUALSPEC/MANUFACTURES CUT SHEETSFOR |
| THE MAIN SW BD AND PROPOSED"KIRK KEY INTERLOCK". |
| PLEASE KNOW, THIS OFFICE HAS SEEN SOME SYSTEMS WHICH DO |
| NOT MEET THE CODE WITH RESPECT TO TRANSFER EQUIPMENT |
| AND LISTED FOR THE INTENDED USE. |
| 702.6, 110.3 |
| |
| 10) NOTE: OK. |
| |
| 11) NOTE: OK. |
| |
| ** NEW NOTE ** |
| |
| 1) NOTE: PLEASE SHOW ANY STROBES/HORN DEVICES NEW OR |
| EXISTING MEETING THE 2004 FBC CHAPTER 11. 11-4.28.1, |
| .2, AND .3(4). |
| THIS WAS NOT IN PREVIOUS REVIEW AS IT HAS NOW BECOME A |
| REQUIRED REVIEW FOR THE ELECTRICAL PLAN REVIEW STAFF. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |