Plan Review Notes For Permit 06070683 |
Permit Number |
06070683 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-10-06 00:00:00 | PROVISO:PLAN CHECK ONLY | | | | 1.PLAN SHEET M1, THE ROOFTOP EQUIPMENT | | PIPING RUNOUT INDICATES 3/4" FOR ALL | | UNITS.PLEASE NOTE, CONDENSATE SHALL BE | | INSTALLED PER MANUFACTURER'S | | SPECIFICATIONS, FULL LINE SIZE FOR | | PROPER DRAINAGE. | | | | 2.ADDITIONAL PERMITS REQUIRED FOR | | HOOD, FIRE SUPPRESSION & WALK-IN | | COOLERS.PLEASE PROVIDE MANUFACTURER'S | | SUBMITTAL DATA WITH PERMIT APPLICATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719 OR | | E-MAIL [email protected]. |
|