2006-10-10 15:14:52 | ******DENIED****** |
| |
| |
| |
| 01.)NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| REFERENCED. |
| |
| 02.)CONSTRUCTION, ALTERATION, AND DEMOLITION |
| OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 03)ON THE APPROPIATE EXTERIOR ELEVATION SHEET, |
| SHOW/DISPALAY THE SUITE UNIT NUMBER OF THIS 6901 |
| OKEECHOBEE BOULEVARD SHOPPING PLAZA.AS PER WEST PALM |
| BEACH CODE, CHARACTERS ( NUMBERS AND/OR LETTERS) SHALL |
| BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH. |
| |
| 04.)SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED |
| FOR FIRE SPRINKLER AND/OR FIRE ALARM SYSTEM |
| MODIFICATION. |
| |
| 05.)FIRE SPRINKLER SHALL BE MAINTAINED OPERATIONAL |
| UNTIL SUCH SUCH TIMETHAT THE SYSTEM IS DEMOLISHED. |
| PRIOR TO THE SPRINKLER SYSTEM BEING TAKEN OUT OF |
| SERVICE, NOTIFICATION AND APPROVAL SHALL BE ATTAINED |
| FROM THE FIRE PREVENTION BUREAU. |
| |
| 06.)DEMOLITION OPERATIONS INVOLVING THE USE OF |
| CUTTING AND WELDING SHALL BE DONE IN ACCORDANCE WITH |
| NFPA 51B. |
| |
| 07.)FIRE ALARM SYSTEM SHALL BE FULLY ADDRESSABLE AND |
| SHALL BE UL CERTIFIED FOR CENTRAL STATION SERVICE. |
| |
| 08.)DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL |
| FIRE ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. |
| |
| 09.)LOCK-BOX ENTRY KEY SYSTEM WILL BE REQUIRED.SHOW |
| THE LOCATION OF THIS DEVICE ON THE APPROPIAITE PLAN |
| SHEET(S). |
| |
| 10.)INTERIOR FINISH FOR WALLS AND CEILINGS SHALL BE |
| CLASS "A" OR CLASS "B". |
| |
| 11.)ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA |
| 80. |
| |
| 12.)PANIC HARDWARE TO BE INSTALLED ON EXIT DOORS WITH |
| AN OCCUPANT LOAD OF ONE HUNDRED PERSONS OR MORE. |
| |
| 13.)SHOW ON THE APPROPIATE FIRE PROTECTION PLAN |
| SHEET(S) THE LOCATION OF THE 2A10BC RATED FIRE |
| EXTINGUISHERS AT DISTANCES TO SATISFY THE 75' TRAVEL |
| DISTANCE REQUIREMENT. |
| |
| |
| |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |
| 561-805-6722 |