2006-08-03 00:00:00 | ********** UNSAT ************* |
| |
| **********WAL-MART NEW /REMODEL****** |
| |
| ** PLEASE SEE PLANS WERE ONLY SUBMITTED |
| FOR "PLAN REVIEW" AND HAVE NOT BEEN |
| SUBMITTED FOR PERMIT. |
| |
| |
| 1) NOTE: PLEASE SEE ALL ARCHITECTURAL |
| SHEETS CONTAIN A RAISED SEAL OVER A |
| "PHOTO-COPIED" SIGNATURE OF THE |
| ARCHITECT OF RECORD. PLEASE KNOW UNDER |
| FS 481.221 AND FAC 61G1-16.004 THE |
| SIGNATURE SHALL BE ORIGINAL. SEALED |
| PHOTO-COPIED PLANS ARE NOT ACCEPTABLE. |
| ** PLEASE KNOW THIS IS REQUIRED FOR ALL |
| TRADES AND FOR ALL SHEETS WHETHER OR NOT |
| COMMENT IS MADE BY OTHER REVIEWER(S). |
| |
| 2) NOTE: PLEASE ALSO SEE "S-1, S-2, AND |
| S-3, AS THESE ALSO CONTAIN A RAISED SEAL |
| OVER A PHOTO-COPIED SIGNATURE> |
| PLEASE SEE FS 472.025, FAC 61G17 |
| REQUIRED FOR BOTH SETS AND WHETHER OR |
| NOT COMMENT IS MADE BY OTHER |
| REVIEWER(S). |
| |
| 3) NOTE: PLEASE SEE MISSING REQUIRED |
| INFORMATION ON TITLE BLOCKS FOR |
| ARCHITECTURAL AND ENGINEERING FIRMS. |
| PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| 61G1-16.004 AND FLORIDA STATUES 481.219 |
| FOR THE ARCHITECTURAL FIRM AND PLEASE |
| SEE FAC61G15-23.002 AND FS 471.023 FOR |
| ENGINEERING FIRM. |
| PLEASE SEE MISSING PRINTED NAME AND |
| LICENSE NUMBER'S FOR INDIVIDUAL |
| DESIGNERS OF RECORD. |
| PLEASE SEE MISSING CERTIFICATE OF |
| AUTHORIZATION NUMBER REQUIRED FOR BOTH |
| FIRMS REQUIRED ON TITLE BLOCKS ALSO. |
| ** PLEASE KNOW THIS IS REQUIRED FOR ALL |
| SHEETS AND FOR ALL TRADES WHETHER OR NOT |
| COMMENT IS MADE BY OTHER REVIEWER(S). |
| |
| 4) NOTE: PLEASE BE SURE PLANS REFLECT |
| THE FOLLOWING CODES AT A MINIMUM. |
| PLEASE SEE PLANS MENTIONS THE 2004 |
| FLORIDA ELECTRICAL CODE, HOWEVER CHAPTER |
| 27 OF THE 2004 FBC ADOPTED THE 2002 |
| NFPA-70 (NEC). |
| PLEASE ALSO LIST THE FOLLOWING. |
| NFPA-72 2002, NFPA-101 2003. |
| |
| 5) NOTE: PLEASE SEE 2004 FBC CHAPTER 13. |
| PLEASE SEE 13-413.1ABC.1, PROVIDE WORST |
| CASE FOR FEEDERS AND BRANCH CIRCUITS. |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3. |
| PLEASE PROVIDE LIGHTING CONTROL/ ENERGY |
| MANG SYSTEM DETAILS. |
| PLEASE SEE 13-415.1.AB.1 , |
| 13-415.2.ABC.1 FOR TABLES 415.2.C.1 AND 415.2.B.1. |
| PLEASE ALSO BE SURE ALL ENERGY |
| CALCULATIONS ARE SIGNED, DATED AND |
| SEALED BY THE DESIGNER(S) OF RECORD. |
| |
| 6) NOTE: PLEASE SEE PANELS IN |
| DELI/BAKERY ARE WHICH DO NOT SEEM TO |
| MEET 110.26 FOR MIN CLEARANCES. |
| |
| 7) NOTE: PLEASE SEE MINIMUM DOOR/ EGRESS REQUIREMENTS |
| SHALL BE REQUIRED FOR MAIN |
| ELECTRICAL ROOM. PLEASE ALSO SEE PANIC |
| HARDWARE AND DOORS CHANGES WILL BE |
| REQUIRED FOR NEW EQUIPMENT. |
| |
| 8) NOTE: PLEASE SEE PANEL WHICH IS BEING |
| SHOWN IN STORAGE ROOM SHALL BE A |
| DEDICATED ELECTRICAL/EQUIPMENT ROOM OR |
| PLEASE RELOCATE PANEL. |
| PLEASE SEE 110.26,408.7, AND 240.24 AS |
| STORAGE OF ANY TYPE FOR MIN CLEARANCES, COMBUSTIBLES OF |
| EASILY IGNITABLE |
| MATERIALS. |
| |
| 9) NOTE: PLEASE SUBMIT ACTUAL |
| SPEC/MANUFACTURES CUT SHEETSFOR THE |
| MAIN SW BD AND PROPOSED"KIRK KEY |
| INTERLOCK". PLEASE KNOW, THIS OFFICE HAS |
| SEEN SOME SYSTEMS WHICH DO NOT MEET THE |
| CODE WITH RESPECT TO TRANSFER EQUIPMENT |
| AND LISTED FOR THE INTENDED USE. |
| 702.6, 110.3 |
| |
| 10) NOTE: PLEASE CLARIFY OF ALL |
| CONTINUOUS LOADS AND LARGEST MOTOR LOADS |
| ARE ALREADY SHOWN AT 125%. |
| 215.3,230.42 ETC |
| PLEASE PROVIDE DETAIL ON LOAD |
| CALCULATIONS. |
| 220. |
| |
| 11) NOTE: PLEASE CLARIFY RECEPTS IN |
| BATH(S) AS GFI PROTECTED OR NOT. |
| PLEASE SEE PANEL SCHEDULE DOES NOT SEEM |
| TO INDICATE THE REQUIRED GFI PROTECTION. |
| 210.8B1 |
| |
| ** PLEASE BE SURE TO SEE ANY POSISBLE |
| COMMENTS FROM OTHER TRADES WHICH MAY |
| AFFECT ELECTRICAL PLANS/DESIGN. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTRUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
2006-08-02 00:00:00 | PLANS WILL BE GOING INTO A "F" STATUS, |
| NOTES TO FOLLOW. |
2006-07-30 00:00:00 | IN ELECTRIC FOR REVIEW, |