Plan Review Notes
Plan Review Notes For Permit 06070683
Permit Number 06070683
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-03 00:00:00********** UNSAT *************
  
 **********WAL-MART NEW /REMODEL******
  
 ** PLEASE SEE PLANS WERE ONLY SUBMITTED
 FOR "PLAN REVIEW" AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT.
  
  
 1) NOTE: PLEASE SEE ALL ARCHITECTURAL
 SHEETS CONTAIN A RAISED SEAL OVER A
 "PHOTO-COPIED" SIGNATURE OF THE
 ARCHITECT OF RECORD. PLEASE KNOW UNDER
 FS 481.221 AND FAC 61G1-16.004 THE
 SIGNATURE SHALL BE ORIGINAL. SEALED
 PHOTO-COPIED PLANS ARE NOT ACCEPTABLE.
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 2) NOTE: PLEASE ALSO SEE "S-1, S-2, AND
 S-3, AS THESE ALSO CONTAIN A RAISED SEAL
 OVER A PHOTO-COPIED SIGNATURE>
 PLEASE SEE FS 472.025, FAC 61G17
 REQUIRED FOR BOTH SETS AND WHETHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 3) NOTE: PLEASE SEE MISSING REQUIRED
 INFORMATION ON TITLE BLOCKS FOR
 ARCHITECTURAL AND ENGINEERING FIRMS.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 AND FLORIDA STATUES 481.219
 FOR THE ARCHITECTURAL FIRM AND PLEASE
 SEE FAC61G15-23.002 AND FS 471.023 FOR
 ENGINEERING FIRM.
 PLEASE SEE MISSING PRINTED NAME AND
 LICENSE NUMBER'S FOR INDIVIDUAL
 DESIGNERS OF RECORD.
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER REQUIRED FOR BOTH
 FIRMS REQUIRED ON TITLE BLOCKS ALSO.
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 4) NOTE: PLEASE BE SURE PLANS REFLECT
 THE FOLLOWING CODES AT A MINIMUM.
 PLEASE SEE PLANS MENTIONS THE 2004
 FLORIDA ELECTRICAL CODE, HOWEVER CHAPTER
 27 OF THE 2004 FBC ADOPTED THE 2002
 NFPA-70 (NEC).
 PLEASE ALSO LIST THE FOLLOWING.
 NFPA-72 2002, NFPA-101 2003.
  
 5) NOTE: PLEASE SEE 2004 FBC CHAPTER 13.
 PLEASE SEE 13-413.1ABC.1, PROVIDE WORST
 CASE FOR FEEDERS AND BRANCH CIRCUITS.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3.
 PLEASE PROVIDE LIGHTING CONTROL/ ENERGY
 MANG SYSTEM DETAILS.
 PLEASE SEE 13-415.1.AB.1 ,
 13-415.2.ABC.1 FOR TABLES 415.2.C.1 AND 415.2.B.1.
 PLEASE ALSO BE SURE ALL ENERGY
 CALCULATIONS ARE SIGNED, DATED AND
 SEALED BY THE DESIGNER(S) OF RECORD.
  
 6) NOTE: PLEASE SEE PANELS IN
 DELI/BAKERY ARE WHICH DO NOT SEEM TO
 MEET 110.26 FOR MIN CLEARANCES.
  
 7) NOTE: PLEASE SEE MINIMUM DOOR/ EGRESS REQUIREMENTS
 SHALL BE REQUIRED FOR MAIN
 ELECTRICAL ROOM. PLEASE ALSO SEE PANIC
 HARDWARE AND DOORS CHANGES WILL BE
 REQUIRED FOR NEW EQUIPMENT.
  
 8) NOTE: PLEASE SEE PANEL WHICH IS BEING
 SHOWN IN STORAGE ROOM SHALL BE A
 DEDICATED ELECTRICAL/EQUIPMENT ROOM OR
 PLEASE RELOCATE PANEL.
 PLEASE SEE 110.26,408.7, AND 240.24 AS
 STORAGE OF ANY TYPE FOR MIN CLEARANCES, COMBUSTIBLES OF
 EASILY IGNITABLE
 MATERIALS.
  
 9) NOTE: PLEASE SUBMIT ACTUAL
 SPEC/MANUFACTURES CUT SHEETSFOR THE
 MAIN SW BD AND PROPOSED"KIRK KEY
 INTERLOCK". PLEASE KNOW, THIS OFFICE HAS
 SEEN SOME SYSTEMS WHICH DO NOT MEET THE
 CODE WITH RESPECT TO TRANSFER EQUIPMENT
 AND LISTED FOR THE INTENDED USE.
 702.6, 110.3
  
 10) NOTE: PLEASE CLARIFY OF ALL
 CONTINUOUS LOADS AND LARGEST MOTOR LOADS
 ARE ALREADY SHOWN AT 125%.
 215.3,230.42 ETC
 PLEASE PROVIDE DETAIL ON LOAD
 CALCULATIONS.
 220.
  
 11) NOTE: PLEASE CLARIFY RECEPTS IN
 BATH(S) AS GFI PROTECTED OR NOT.
 PLEASE SEE PANEL SCHEDULE DOES NOT SEEM
 TO INDICATE THE REQUIRED GFI PROTECTION.
 210.8B1
  
 ** PLEASE BE SURE TO SEE ANY POSISBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS/DESIGN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
2006-08-02 00:00:00PLANS WILL BE GOING INTO A "F" STATUS,
 NOTES TO FOLLOW.
2006-07-30 00:00:00IN ELECTRIC FOR REVIEW,