Plan Review Notes For Permit 06070610 |
Permit Number |
06070610 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-07-13 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1- FLAT ROOF SYSTEM: A) DADE COUNTY NOA | | 03-0430.13 PACKAGE SUBMITTED SHOWS | | SELECTED APPROVED ASSEMBLY ON PAGE 27 | | FOR CONCRETE DECK, NON INSULATED | | ASSEMBLY. BUT, THERE IS ADDITIONAL | | INFORMATION SUBMITTED FOR INSULATION. | | NEED TO BE SPECIFIC ON WHICH ASSEMBLY IS | | GOING TO BE INSTALLED. INSULATED OR | | NON-INSULATED IN ORDER TO CHECK | | COMPLIANCE WITH GENERAL LIMITATION #7 OR | | #9 ON LAST PAGE OF NOA. SEE ATTACHED | | COPY OF CITY POLICY FOR RE-ROOFS PERMITS | | FOR REQUIRED INFORMATION TO BE | | SUBMITTED. | | B) PROVIDE COPY OF COVER PAGE OF | | FLORIDA PRODUCT APPROVAL FL-617 WHICH IS | | THE ONE THAT MATCHES THIS NOA. | | C) IF SELECTING AN INSULATED ASSEMBLY, | | THEN CLEARLY MARK WHICH INSULATION | | ASSEMBLY IS GOING TO BE INSTALLED. | | | | 2- DADE COUNTY NOA 01-1226.03 FOR ELK | | PRESTIQUE SHINGLES IS EXPIRED. PROVIDE | | CURRENT NOA. | | | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|