2006-07-13 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- FLAT ROOF SYSTEM: A) DADE COUNTY NOA |
| 03-0430.13 PACKAGE SUBMITTED SHOWS |
| SELECTED APPROVED ASSEMBLY ON PAGE 27 |
| FOR CONCRETE DECK, NON INSULATED |
| ASSEMBLY. BUT, THERE IS ADDITIONAL |
| INFORMATION SUBMITTED FOR INSULATION. |
| NEED TO BE SPECIFIC ON WHICH ASSEMBLY IS |
| GOING TO BE INSTALLED. INSULATED OR |
| NON-INSULATED IN ORDER TO CHECK |
| COMPLIANCE WITH GENERAL LIMITATION #7 OR |
| #9 ON LAST PAGE OF NOA. SEE ATTACHED |
| COPY OF CITY POLICY FOR RE-ROOFS PERMITS |
| FOR REQUIRED INFORMATION TO BE |
| SUBMITTED. |
| B) PROVIDE COPY OF COVER PAGE OF |
| FLORIDA PRODUCT APPROVAL FL-617 WHICH IS |
| THE ONE THAT MATCHES THIS NOA. |
| C) IF SELECTING AN INSULATED ASSEMBLY, |
| THEN CLEARLY MARK WHICH INSULATION |
| ASSEMBLY IS GOING TO BE INSTALLED. |
| |
| 2- DADE COUNTY NOA 01-1226.03 FOR ELK |
| PRESTIQUE SHINGLES IS EXPIRED. PROVIDE |
| CURRENT NOA. |
| |
| 3- NOTICE OF COMMENCEMENT IS EXPIRED |
| AFTER 90 DAYS IF WORK IS NOT STARTED. |
| SEE FLORIDA STATUTES SEC. 713.13(2). |
| NEED RE-RECORDED N.O.C. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |