Date |
Text |
2006-09-12 00:00:00 | ******DENIED 2ND TIME****** |
| REFERENCE: FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| |
| THE FOLLOWING INFORMATION IS STILL |
| REQUIRED FOR GAS PLAN REVIEW: (NOTE: |
| PREVIOUS COMMENTS WERE NOT ADDRESSED) |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| NOTE: THE RESUBMITTED DRAWINGS ONLY |
| INDICATES THE MEASUREMENT OF THE |
| UNDERGROUND PE PIPING. WHAT ARE THE CUT |
| SECTION MEASUREMENTS OF THE ABOVE GROUND |
| PIPING? |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| NOTE: THE RESUBMITTED DRAWINGS ONLY |
| INDICATE THE UNDER GROUND MATERIAL AND |
| SIZE. WHAT IS THE SIZE AND MATERIAL OF |
| THE ABOVE GROUND PIPING? |
| |
| 3. TYPE OF GAS, (LP OR NATURAL) |
| NOTE: THE RESUBMITTED DRAWINGS DO NOT |
| INDICATE THE GAS TYPE. |
| |
| 4. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| NOTE: RECORDS INDICATE EXISTING GAS TO A |
| 40 GAL. NAT. GAS WATER HEATER, PLEASE |
| REFERENCE THE ATTACHED PERMIT |
| INFORMATION INDICATING GAS AT SAID |
| ADDRESS. THE BTU LOAD OF THE EXISTING AS |
| WELL AS THE NEW PROPOSED GENERATOR BTU,S |
| NEED TO BE INDICATED ON THE DRAWINGS. |
| |
| 5. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| NOTE: GAS SYSTEMS ARE SIZED BY THE |
| LONGEST LENGTH METHOD. AGAIN THE |
| EXISTING GAS SYSTEM NEEDS TO BE |
| INDICATED ON THE DRAWING WITH ITS |
| MEASUREMENTS. |
| |
| 6. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| NOTE: THE RESUBMITTED DRAWINGS DO NOT |
| INDICATE THE DELIVERY PRESSURE. |
| |
| 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2 |
| NOTE: RESUBMITTED DRAWINGS DO NOT |
| INDICATE THE DELIVERY PRESSURE, BUT IF |
| PRESSURE IS 2LB, PLEASE SUBMIT |
| MANUFACTURER CUT SHEETS OF REGULATORS. |
| |
| 8. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| NOTE: THE RESUBMITTED DRAWINGS DO NOT |
| HAVE THE PRINTED NAME, SIGNED NAME OF |
| THE PERSON RESPONSIBLE FOR DRAWING, OR |
| THE DATE. |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |