Plan Review Notes
Plan Review Notes For Permit 06070580
Permit Number 06070580
Review Stop G
Sequence Number 2
Notes
Date Text
2006-09-12 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR GAS PLAN REVIEW: (NOTE:
 PREVIOUS COMMENTS WERE NOT ADDRESSED)
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE RESUBMITTED DRAWINGS ONLY
 INDICATES THE MEASUREMENT OF THE
 UNDERGROUND PE PIPING. WHAT ARE THE CUT
 SECTION MEASUREMENTS OF THE ABOVE GROUND
 PIPING?
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: THE RESUBMITTED DRAWINGS ONLY
 INDICATE THE UNDER GROUND MATERIAL AND
 SIZE. WHAT IS THE SIZE AND MATERIAL OF
 THE ABOVE GROUND PIPING?
  
 3. TYPE OF GAS, (LP OR NATURAL)
 NOTE: THE RESUBMITTED DRAWINGS DO NOT
 INDICATE THE GAS TYPE.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: RECORDS INDICATE EXISTING GAS TO A
 40 GAL. NAT. GAS WATER HEATER, PLEASE
 REFERENCE THE ATTACHED PERMIT
 INFORMATION INDICATING GAS AT SAID
 ADDRESS. THE BTU LOAD OF THE EXISTING AS
 WELL AS THE NEW PROPOSED GENERATOR BTU,S
 NEED TO BE INDICATED ON THE DRAWINGS.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: GAS SYSTEMS ARE SIZED BY THE
 LONGEST LENGTH METHOD. AGAIN THE
 EXISTING GAS SYSTEM NEEDS TO BE
 INDICATED ON THE DRAWING WITH ITS
 MEASUREMENTS.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 NOTE: THE RESUBMITTED DRAWINGS DO NOT
 INDICATE THE DELIVERY PRESSURE.
  
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: RESUBMITTED DRAWINGS DO NOT
 INDICATE THE DELIVERY PRESSURE, BUT IF
 PRESSURE IS 2LB, PLEASE SUBMIT
 MANUFACTURER CUT SHEETS OF REGULATORS.
  
 8. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
 NOTE: THE RESUBMITTED DRAWINGS DO NOT
 HAVE THE PRINTED NAME, SIGNED NAME OF
 THE PERSON RESPONSIBLE FOR DRAWING, OR
 THE DATE.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  
  
  
  
  