Plan Review Notes For Permit 06070579 |
Permit Number |
06070579 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-07-16 00:00:00 | ** UNSAT ** | | | | 1) NOTE: PLEASE SPECIFY EXISTING | | OCCUPANCY. PLEASE STATE IF THE EXISTING | | OCCUPANCY IS CHANGING OR EXISTING TO | | REMAIN AND STATE THAT OCCUPANCY. | | FBC 105.1 ADMIN SECT. | | | | | | 2) NOTE: PLEASE PROVIDE AIC RATINS FOR | | NEW SERVICE MAINS/EEQUIPMENT PER 110.9 | | FBC 106.1.2 ADMIN SECT. | | | | 3) NOTE: PLEASE PROVIDE LOCATION OF NEW | | PANELS BEING INSTALLED. | | NEED TO VERIFY 110.26,240.24,408.7 ETC. | | | | 4) NOTE: PLEASE PROIDE A SIGNED CONTRACT | | FOR SCOPE OF WORK BEING DONE AS VALUE | | SEEMS LOW. | | FBC 108.3. | | | | 5) NOTE: PLEASE SEE FBC 106.1.2 AS THE | | PLANS ARE REQUIRED TO CONTAIN THE | | CLEARLY PRINTED NAME AND SIGNATURE OF | | THE PERSON RESPONSIBLE FOR PLANS/DESIGN. | | | | 6) NOTE: PLEASE SEE THAT ALL CONTINUOUS | | LOADS ARE TO BE SHOWN AT 125%, | | 215.3,230.42 ALONG WITH LARGEST MOTOR | | LOADS. | | | | 7) NOTE: PLEASE SEE 424.3B FOR MIN OCP | | AND AWG FOR 10KW A/C UNITS. | | (60A MIN). | | 240.4,310.16 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | | | | | |
|