Plan Review Notes
Plan Review Notes For Permit 06070579
Permit Number 06070579
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-16 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SPECIFY EXISTING
 OCCUPANCY. PLEASE STATE IF THE EXISTING
 OCCUPANCY IS CHANGING OR EXISTING TO
 REMAIN AND STATE THAT OCCUPANCY.
 FBC 105.1 ADMIN SECT.
  
  
 2) NOTE: PLEASE PROVIDE AIC RATINS FOR
 NEW SERVICE MAINS/EEQUIPMENT PER 110.9
 FBC 106.1.2 ADMIN SECT.
  
 3) NOTE: PLEASE PROVIDE LOCATION OF NEW
 PANELS BEING INSTALLED.
 NEED TO VERIFY 110.26,240.24,408.7 ETC.
  
 4) NOTE: PLEASE PROIDE A SIGNED CONTRACT
 FOR SCOPE OF WORK BEING DONE AS VALUE
 SEEMS LOW.
 FBC 108.3.
  
 5) NOTE: PLEASE SEE FBC 106.1.2 AS THE
 PLANS ARE REQUIRED TO CONTAIN THE
 CLEARLY PRINTED NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR PLANS/DESIGN.
  
 6) NOTE: PLEASE SEE THAT ALL CONTINUOUS
 LOADS ARE TO BE SHOWN AT 125%,
 215.3,230.42 ALONG WITH LARGEST MOTOR
 LOADS.
  
 7) NOTE: PLEASE SEE 424.3B FOR MIN OCP
 AND AWG FOR 10KW A/C UNITS.
 (60A MIN).
 240.4,310.16
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  