Plan Review Notes
Plan Review Notes For Permit 06070542
Permit Number 06070542
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-16 00:00:00** UNSAT **
  
  
 1) NOTE: PLEASE KNOW AS PER THE
 "RED-TAG" CORRECTION NOTICE ATTACHED TO
 PERMIT APPLICATION, MUST FIRST OBTAIN A
 PERMIT FOR THE INSTALLATION OF THE SPA
 AND DECK BEFORE AN ELECTRICAL PERMIT CAN
 BE ISSUED.
 105.1
  
 2) NOTE: PLEASE CLARIFY AND CORRELATE
 LOADS ON CALCUALTIONS. PLEASE SEE RISER
 SUBMITTED INDICATES 38A'S, HOWEVER LOAD
 INDICATED ONLY @ 5200VA? . PLEASE SEE
 5200VA DIVIDED BY 240, DOES NOT COME UP
 TO 38A'S??
 PLEASE ALSO SEE LOAD SHOWN ON LEFT HAND
 SIDE OF CALCS MENTIONS 6KW?
 IS THE "ADD HEAT" MEANT TO BE A/C HEAT?
 220.31B
  
 3) NOTE: PLEASE KNOW, DISCONNECT IS
 REQUIRED WITHIN USER READLIY ACCESSIBLE
 LOCATION "WITHIN SIGHT" HOWEVER MORE
 THAN 5'. 680.41
  
 4) NOTE: PLEASE BE SURE ALL PLANS
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR
 PLANS/DESIGN. FBC 106.1.2 ADMIN SECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  