2006-08-07 00:00:00 | ***** UNSAT2ND REVIEW ***** |
| |
| PLEASE SEE SOME NOTES FROM PREVIOUS |
| REVIEW STILL NEED TO NE VERIFIED ETC. |
| |
| 1) NOTE: NO, PLEASE SEE SPECS UBMITTED |
| DO NOT SEEM TO CONTAIN THE DISCONNECITNG |
| MEANS AS REQUIRED. IF THIS UNIT IS ONE |
| OF THE NEW ONES WHICH CONTAINS A BRKR |
| FOR NORMAL SIDE AND AND ADDTIONAL BRKR |
| FOR EM/GEN SIDE, PLEASE BE SURE SPECS |
| CLEARLY SHOW THIS. |
| PLEASE KNOW, MANY OF GENERAC'S ONLY |
| DISCONNECT POWER FROM THE NORMAL SIDE. |
| THE TOGGLE SWITCH LOCATED IN SOME DO NOT |
| MEET CODE. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE CLARIFY THE USE OF A SE |
| RATED ATS. PLEASE SEE THE EXISTING MAIN |
| FOR HOUSE IS STILL THE SERVICE MAIN. |
| PLEASE SEE THAT THE ATS AS SPECIFIED |
| DOES NOT DICONNECT POWER FROM GEN OR |
| FEEDERS COMING FROM THE GEN AS REQUIRED |
| PER 225.31-225.39. |
| |
| 2) NOTE:NO, PLEASE SEE I COULD NOT |
| LOCATE THE MIN CLEARENCE REQUIRED FOR |
| THIS GEN IN THE SPECS. PLEASE KNOW, THIS |
| OFFICE HAS OBTAINED LTR FROMGENERAC |
| WHICH REQUIRES A MIN OF 5' FOR THIS TYOE |
| OF GEN. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE PROVIDE ALL THE SETBACKS |
| AND DISTANCES AROUND GENERATOR. |
| PLEASE SEE THAT THE SPECS PROVIDE |
| INFORMATION ON MIN CLEARENCES. |
| 110.3, 90.7 |
| |
| 3) NOTE: OK. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |