Plan Review Notes
Plan Review Notes For Permit 06070539
Permit Number 06070539
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-07 00:00:00***** UNSAT2ND REVIEW *****
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO NE VERIFIED ETC.
  
 1) NOTE: NO, PLEASE SEE SPECS UBMITTED
 DO NOT SEEM TO CONTAIN THE DISCONNECITNG
 MEANS AS REQUIRED. IF THIS UNIT IS ONE
 OF THE NEW ONES WHICH CONTAINS A BRKR
 FOR NORMAL SIDE AND AND ADDTIONAL BRKR
 FOR EM/GEN SIDE, PLEASE BE SURE SPECS
 CLEARLY SHOW THIS.
 PLEASE KNOW, MANY OF GENERAC'S ONLY
 DISCONNECT POWER FROM THE NORMAL SIDE.
 THE TOGGLE SWITCH LOCATED IN SOME DO NOT
 MEET CODE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY THE USE OF A SE
 RATED ATS. PLEASE SEE THE EXISTING MAIN
 FOR HOUSE IS STILL THE SERVICE MAIN.
 PLEASE SEE THAT THE ATS AS SPECIFIED
 DOES NOT DICONNECT POWER FROM GEN OR
 FEEDERS COMING FROM THE GEN AS REQUIRED
 PER 225.31-225.39.
  
 2) NOTE:NO, PLEASE SEE I COULD NOT
 LOCATE THE MIN CLEARENCE REQUIRED FOR
 THIS GEN IN THE SPECS. PLEASE KNOW, THIS
 OFFICE HAS OBTAINED LTR FROMGENERAC
 WHICH REQUIRES A MIN OF 5' FOR THIS TYOE
 OF GEN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE ALL THE SETBACKS
 AND DISTANCES AROUND GENERATOR.
 PLEASE SEE THAT THE SPECS PROVIDE
 INFORMATION ON MIN CLEARENCES.
 110.3, 90.7
  
 3) NOTE: OK.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW