Plan Review Notes For Permit 06070539
Permit Number 06070539
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-21 00:00:00***** UNSAT *****
  
 1) NOTE: PLEASE CLARIFY THE USE OF A SE
 RATED ATS. PLEASE SEE THE EXISTING MAIN
 FOR HOUSE IS STILL THE SERVICE MAIN.
 PLEASE SEE THAT THE ATS AS SPECIFIED
 DOES NOT DICONNECT POWER FROM GEN OR
 FEEDERS COMING FROM THE GEN AS REQUIRED
 PER 225.31-225.39.
  
 2) NOTE: PLEASE PROVIDE ALL THE SETBACKS
 AND DISTANCES AROUND GENERATOR.
 PLEASE SEE THAT THE SPECS PROVIDE
 INFORMATION ON MIN CLEARENCES.
 110.3, 90.7
  
 3) NOTE: PLEASE KNOW, LOCATION OF JOB IS
 IN A FLOOD ZONE AND NEEDS TO SPECIFY THE
 MIN HEIGHT OF THE SLAB 6" ABOVE BFE BASE
 FLOOD ELEVATION.
 PLEASE ALSO KNOW, A "FLOOD ELEVATION
 CERTIFICATE" WILL ALSO BE REQUIRED
 BEFORE FINAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717