Date |
Text |
2006-11-02 15:40:03 | |
| |
| 1) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT BEFORE A |
| PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| NOT ACTUALLY COMMENCED |
| WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. |
| |
| 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| PER 108.3 FBC* |
| |
| 3)2004 FL. BLD CODE 1603.1.4 THE |
| FOLLOWING INFORMATION RELATED TO WIND |
| SHALL BE SHOWN ON THE CONSTRUCTION |
| DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| |
| 4)1609.1.3 ANCHORAGE AGAINST OVERTURNING, UPLIFT AND |
| SLIDING. |
| STRUCTURAL MEMBERS AND SYSTEMS AND COMPONENTS AND |
| CLADDING IN A BUILDING OR STRUCTURE SHALL BE ANCHORED |
| TO RESIST WIND-INDUCED OVERTURNING, UPLIFT AND SLIDING |
| AND TO PROVIDE CONTINUOUS LOAD PATHS FOR THESE FORCES |
| TO THE FOUNDATION. WHERE A PORTION OF THE RESISTANCE TO |
| THESE FORCES IS PROVIDED BY DEAD LOAD, THE DEAD LOAD, |
| INCLUDING THE WEIGHT OF SOILS AND FOUNDATIONS, SHALL BE |
| TAKEN AS THE MINIMUM DEAD LOAD LIKELY TO BE IN PLACE |
| DURING A DESIGN WIND EVENT. WHERE THE ALTERNATE BASIC |
| LOAD COMBINATIONS OF SECTION 1605.3.2 ARE USED, ONLY |
| TWO-THIRDS OF THE MINIMUM DEAD LOAD LIKELY TO BE IN |
| PLACE DURING A DESIGN WIND EVENT SHALL BE USED. NOTE: |
| AN ENGINEER OR ARCHITECT WHO IS REGISTERED WITH THE |
| STATE WILL HAVE TO PROVIDE THIS INFORMATION ON THE |
| DRAWINGS. SEE F.A.C. 61G15-23.002 - 471.025 F.S. AND |
| SEC. 106 F.B.C. |
| |
| 5) THE SLAB DETAIL IS STILL MISSING FROM THE DRAWINGS. |
| THE SCALE NOTED ON THEDRAWINGS IS INCORRECT. INDICATE |
| THE CORRECT SCALE FOR THE DRAWINGS 106.1.3 FBC* |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| 805-6726 |
| |
| |