2006-07-30 00:00:00 | ******** UNSAT ************ |
| |
| 1) NOTE: PLEASE SUBMIT COMPLETED PLANS |
| WHICH ARE DONE WITH DRAFTMAN'S QUALITY |
| WITH MIN SCALE AS REQUIRED. |
| PLEASE SEE NO ELECTRICAL RISER DIAGRAM |
| WAS SUBMITTED FOR REVIEW. |
| DRAWING SUBMITTED DOES NOT SHOW OR |
| INCLUDE CONDUCTORS, CONDUITS, MAINS, ALL |
| SIZES, DISCONNECTING MEANS REQUIRED, |
| ATS.MTS, GROUNDING, ETC ETC. |
| PLEASE SEE FBC 106.1.2, 106.1.3 AND |
| SUBMIT COMPLETE PLANS. |
| PLEASE ALSO SEE NEC 2002, |
| 250,225.31-225.39, 230.72, 702, 215.5 |
| 240.4,310.16 ETC |
| |
| 2) NOTE:PLEASE SEE BLDG REVIEW |
| COMMENTS FOR MISSING SLAB DETAIL. |
| PLEASE ALSO SEE LOCATION APPEARS TO BE |
| IN A FLOOD ZONE "A".PLEASE BE SURE |
| ELEVATION OF GENERATOR IS A MIN OF 6" |
| ABOVE BFE. |
| PLEASE BE SURE SITE/SURVEY AND NEW PLANS |
| DETAIL THIS. |
| |
| 3) NOTE: PLEASE SEE VALUE FOR PROJECT |
| AND SCOPE OF WORK IS REQUIRED TO INCLUDE |
| ALL LABOR AND MATERIALS EVEN IF ANY |
| EQUIPMENT IS OWNER SUPPLIED. |
| FBC 108.3 |
| PLEASE SEE VLAUE IS WAY LOW.PLEASE BE |
| SURE TO ADJUST VALUE BEFORE RESUBMITTING |
| PLANS ONCE ALL REVIEWS ARE DONE. PLEASE |
| KNOW, A VALUE BASED ON THE MARSHALL'S |
| /SWIFT GUIDE ADOPTED INTO THE FBC MAY BE |
| USED TO ASSESS A VALUE. |
| |
| 4) NOTE: PLEASE SUBMIT ALL MANUFACTURE |
| SPECS/CUT SHEETS FOR ALL EQUIPMENT. |
| PLEASE SEE MISSING SPEC FOR THE MTS/ATS. |
| |
| 5) NOTE: PLEASE SEE THAT ALL PLANS SHALL |
| CONTAIN THE PRINTED NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR PLANS/ |
| DESIGN. THIS IS REQUIRED FOR ALL SHEETS. |
| PLEASE SEE FBC106.1.2 OR PLEASE SEE FS |
| 481,471 IF PLANS ARE DONE BY AN |
| ARCHITECT OR ENGINEER. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| |