2006-08-22 00:00:00 | BUILDING REVIEW 3RD CHECKLIST: |
| |
| TRUSS PACKAGE: |
| 1- ENGINEER TO PROVIDE ALL HIS |
| INFORMATION IN ALL DWGS AS REQ'D BY |
| CHAPTER 471 FL. ST. & SEC. 61G15-23.002 |
| OF FLORIDA ADMINISTRATIVE CODE. |
| |
| ***NO DONE. |
| |
| 2- ALL ENGINEER DRAWINGS AND LETTERS |
| NEED TO BE SIGNED AND SEALED AS REQUIRED |
| BY CHAPTER 471 FL. ST. AND 61G15-23.002, |
| INCLUDING ALL GENERAL NOTES AND GENERAL |
| DETAILS. |
| |
| ***NO DONE. |
| |
| 3- A) GENERAL DETAILS NEED TO BE |
| UPDATED. FBC 2004 CALLS FOR ASCE 7-02, |
| NOT ASCE 7-98. ENGINEER TO UPDATE ALL |
| DRAWINGS. |
| |
| ***NO DONE. |
| |
| B) PROVIDE ONLY THE DETAILS THAT |
| APPLY TO THIS JOB. PLEASE, DON'T PROVIDE |
| UNNECESSARY INFORMATION TO EXPEDITE THE |
| REVIEW PROCESS. |
| |
| ***OK. |
| |
| 4- DESIGN LOADS SHOWN IN TRUSS LAYOUT, |
| ENGINEERED TRUSS AND GENERAL DRAWINGS |
| NEED TO MATCH. REVISE AS REQUIRED. |
| |
| |
| ***NO DONE. |
| |
| 5- SPECIFY ROOF SHEATHING NAILING. SEE |
| TABLE 2304.9.1 FBC 2004. |
| |
| ***OK. |
| |
| 6- SPECIFY TRUSS TO WALL CONNECTORS AND |
| PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL AS REQUIRED BY RULE 9B-72. GO |
| TO WWW.FLORIDABUILDING.ORG TO DOWNLOAD |
| PRODUCT APPROVALS. |
| |
| *** DRAWING 11A BY THE ENGINEER JOHN |
| HOLT AND TRUSS LAYOUT DON'T MATCH. TRUSS |
| LAYOUT CALLS FOR RAKED BEAM, WHILE |
| DRAWING 11A CALLS FOR GABLE END TRUSS. |
| THERE IS NOT GABLE END TRUSS. ENGINEER |
| DRAWING 11A AND TRUSS DRAWINGS TO MATCH. |
| ***NOTE: MAKE SURE DRAWING 11A IS |
| LEGIBLE. |
| |
| 7- ROOF PITH OF 2.5:12 REQUIRES 2 LAYERS |
| OF UNDERLAYMENT. SEC. 1507.2.2 FBC 2004. |
| |
| ***OK. |
| |